PAP Precision Air Processor for Facility Use with Temperature and Humidity Control / Air Cooled Design / Remote Condenser For Constant Temperature and Constant Humidity Room and Cleanroom
PAP20A1-KR / PAP40C1-KR
PAP80B1-KR / PAP120A1-KR
(Remote Condenser Type)
- Air Processing Capacity
- 20 to 120 m3/min ※ 3 to 15 hp
- Temperature and Humidity Control Precision
- ±0.2℃
- Temperature Setting Range
- 18 to 30℃
- Humidity Control Precision
- ±2%
- Possible Humidity Setting Range
- 45 to 60%
- Offers Energy Savings up to 80% AND High Precision Air Processing
- Heat Pump Balance Control
(Super Reheat Spec. Models)
+Inverter Speed Control
-
Temperature Control -
Humidity Control -
Intelligent Monitor -
Capacity Control
Features
The PAP-R Series: Offering One Rank Up in High Precision Air Processing
Integrated Design Saves Space and Eases Installation
Convenient All-In-One Design
Previous Air Processors
Each component takes up valuable space.
PAP-R Facility-Use Precision Air Processor
All-in-one design saves space and makes installation easy.
Environmentally Friendly and Ultra-Energy-Saving Design
Optional Equipment
Optional Equipment and Parts
For Precision Air Processing Applications in Every Field
ORION has many items in addition to the optional equipment shown below to suit our users' environment, needs, and demands. Please feel free to contact your dealer with any questions.
Applications
Application Examples
- Cleanroom (Pharmaceutical, Cosmetic Production Etc.)
- Precision Measurement Room (3-D Measurement Instruments, Tensile Testing Equipment, Laser Measurement Instruments, etc.)
- Precision Processing Room (Nano Processing Equipment, Electrical Discharge Machines, etc.)
- Storage of all kinds of Materials...etc.
- Plant Cultivation Room / Plant Factory...etc.
Every kind of system that meets our users demands.
System Installation Examples
① Outlet Control Method
② Intake Control Method
Installation Examples
Specifications
| Temperature Control Type | ||||
|---|---|---|---|---|
| PAP20A1-KR | PAP40C1-KR | |||
| Performance Specifications |
Possible Setting Range (Circulation Specifications) ※1 |
℃,% | 18 to 30 , 45 to 60 | |
| Temperature Control Precision ※2,13 | ℃,% | ±0.2 , ±2.0 | ||
| Cooling Capacity (50/60 Hz) ※3 | kW | 8.0 | 12.0 | |
| Heating Capacity (50/60 Hz) ※4 | kW | 3.0 | 5.0 | |
| Rated Processing Airflow | m3/min | 20 to 23 | 40 to 45 | |
| Maximum External Static Pressure(50/60 Hz) ※5 | Pa | 200 | ||
| Environmental Conditions |
Indoor Unit Installation Temperature Conditions | ℃ | 5 to 35 | |
| Outdoor Unit Installation Temperature Conditions | ℃ | -5 to 43 | ||
| Temperature Gradient at Intake | ℃/h | Within ±2 | ||
| Humidity Gradient at Intake | %/h | Within ±5 | ||
| External Dimensions |
Indoor Unit (HxDxW) ※6 | mm | 1800×555×980 | 1800×555×1100 |
| Outdoor Unit (HxDxW) ※6 | mm | 824×420×810 | 1160×420×810 | |
| Humidifier (HxDxW) ※6 | mm | 960×520×300 | ||
| Product Mass | Indoor Unit | kg | 240 | 260 |
| Outdoor Unit (H×D×W) | kg | 65 | 80 | |
| Humidifier | kg | 37 | ||
| Humidifier | Water Quality | Deionized water (electrical conductivity: 1 ~ 10 μS/cm) | ||
| Humidification Capacity ※7 | kg/h | 5 | 8 | |
| Power Specific | Power Supply ※8 | V(Hz) | Three-phase 200 ± 10 % (50/60) | |
| Power Consumption (50/60 Hz) (When Auxiliary Heater is Off) ※9 |
kW | 10.9 / 12.7 | 15.0 / 18.0 | |
| Operating Current (50/60 Hz) (When Auxiliary Heater is Off) ※9 |
A | 35 / 40 | 53 / 62 | |
| Power Supply Capacity ※10 | kVA | 15.7 | 21.5 | |
| Sound Pressure Level | Indoor Unit (50/60 Hz) ※11 | dB | 68 or less | 69 or less |
| Outdoor Unit (50/60 Hz) ※11 | dB | 59 or less | ||
| Compressor Output | kW | 1.7 | 3.0 | |
| Blower Fan | Indoor Unit ※12 | kW | 0.4 | |
| Outdoor Unit ※12 | kW | 0.2 | 0.1×2 | |
| Auxiliary Heater | kW | 1.8 | 3.0 | |
| Refrigerant | R410A | |||
| Refrigerant Filling Volume | 2.55 | 3.51 | ||
| Temperature Control Type | ||||
|---|---|---|---|---|
| PAP80B1-KR | PAP120A1-KR | |||
| Performance Specifications |
Possible Setting Range (Circulation Specifications) ※1 |
℃,% | 18 to 30 , 45 to 60 | |
| Temperature Control Precision ※2,13 | ℃,% | ±0.2 , ±2.0 | ||
| Cooling Capacity (50/60 Hz) ※3 | kW | 25 | 38 | |
| Heating Capacity (50/60 Hz) ※4 | kW | 13.0 | 14.5 | |
| Rated Processing Airflow | m3/min | 75 to 80 | 110 to 120 | |
| Maximum External Static Pressure(50/60 Hz) ※5 | Pa | 400 | ||
| Environmental Conditions |
Indoor Unit Installation Temperature Conditions | ℃ | 5 to 35 | |
| Outdoor Unit Installation Temperature Conditions | ℃ | -5 to 43 | ||
| Temperature Gradient at Intake | ℃/h | Within ±2 | ||
| Humidity Gradient at Intake | %/h | Within ±5 | ||
| External Dimensions |
Indoor Unit (HxDxW) ※6 | mm | 1800×600×1500 | 1870×790×1900 |
| Outdoor Unit (HxDxW) ※6 | mm | 1420×800×870 | 1420×800×870× 2units | |
| Humidifier (HxDxW) ※6 | mm | 960×590×500 | 960×790×550 | |
| Product Mass | Indoor Unit | kg | 400 | 700 |
| Outdoor Unit (H×D×W) | kg | 130 | 130×2 | |
| Humidifier | kg | 61 | 90 | |
| Humidifier | Water Quality | Deionized water (electrical conductivity: 1 – 10 μS/cm) | ||
| Humidification Capacity ※7 | kg/h | 20 | 28 | |
| Power Specific | Power Supply ※8 | V(Hz) | Three-phase 200 ± 10 % (50/60) | |
| Power Consumption (50/60 Hz) (When Auxiliary Heater is Off) ※9 |
kW | 26 / 32 | 45 / 54 | |
| Operating Current (50/60 Hz) (When Auxiliary Heater is Off) ※9 |
A | 86 / 104 | 165 / 193 | |
| Power Supply Capacity ※10 | kVA | 38 | 66 | |
| Sound Pressure Level | Indoor Unit (50/60 Hz) ※11 | dB | 69 or less | |
| Outdoor Unit (50/60 Hz) ※11 | dB | 59 or less | ||
| Compressor Output | kW | 4.6 | 7.5 | |
| Blower Fan | Indoor Unit ※12 | kW | 2.2 | 3.75 |
| Outdoor Unit ※12 | kW | 0.75 | 0.75×2 | |
| Auxiliary Heater | kW | 6.0 | 9.0 | |
| Refrigerant | R410A | R407C | ||
| Refrigerant Filling Volume | 5.8 | 12 | ||
- The temperature and humidity control range noted does not necessarily indicate the actual controllable range possible. The range of control depends on the condition of the air supplied at the intake
- When the intake air temperature and humidity, and outdoor ambient temperature are stable. Noted precision is based on measurement by the internal controller at a single air outlet point.
- When operating according to JIS B 8616.The displayed performance will be at least 80% when the intake air temperature of the outdoor unit is at least 35 ˚C.
- When operating according to JIS B 8616.The displayed performance will be at least 75 % when the intake air temperature of the indoor unit is below 20 ˚C.The compressor will stop, and exclusive operation of the auxiliary heater may occur if the control air intake temperature drops to approx. 15 ˚C or lower.
- External dimensions do not include miscellaneous protrusions such as eyebolts, etc.
- Maximum value within the range of unit specifications. Starting current is equal to or less than the operating current.
- The noted external static pressure is when the controlled air is regulated at the outlet to produce the maximum rated processing air flow.
- Measured value (A scale) when operating at the rated processing air flow, at a position of non-resonance, 1 m from the front face of the indoor unit, and at 1 m from the front face of the outdoor unit, at a height of 1.5 m.
- The figure noted is when the equipment is operating at the highest level of humidification.operating at the highest capacity of its normal operating range.
- Noise level can be decreased by installing a noise reducing duct.
- Blower fan output cannot be increased.
- Use the measured temperature and humidity bias function to correct any error between the temperature and humidity shown on the control panel and the user's measured temperature and humidity.
- This product does not detect electrical shorts and does not have a protection function against them. An earth leakage breaker must be installed on the primary side of the power supply.
- All ducting should be insulated and ducting length should be kept as short as possible. (5 m or shorter recommended.)