PAP Precision Air Processor for Facility Use with Temperature Control / Air Cooled Design / Remote Condenser For Constant Temperature Rooms and Cleanrooms
PAP20A-R / PAP40C-R
PAP80B-R / PAP120A-R
(Remote Condenser Type)
- Air Processing Capacity
- 20 to 120 m3/min ※ 3 to 15 hp
- Temperature and Humidity Control Precision
- ±0.2℃
- Temperature Setting Range
- 18 to 30℃
- Offers Energy Savings up to 80% AND High Precision Air Processing
- Heat Pump Balance Control +
Inverter Speed Control
Features
The PAP-R Series: Offering One Rank Up in High Precision Air Processing
Integrated Design Saves Space and Eases Installation
Convenient All-In-One Design
Previous Air Processors
Each component takes up valuable space.
PAP-R Facility-Use Precision Air Processor
All-in-one design saves space and makes installation easy.
Environmentally Friendly and Ultra-Energy-Saving Design
Optional Equipment
Optional Equipment and Parts
For Precision Air Processing Applications in Every Field
ORION has many items in addition to the optional equipment shown below to suit our users' environment, needs, and demands. Please feel free to contact your dealer with any questions.
<Part Name>
- Plenum Chamber with HEPA Filter Assembly
- Plenum Chamber Assembly
- Rear Intake Unit Assembly
- Front Intake Noise Reduction Chamber Assembly
- Drain-Up Unit (Incl. PVC Piping Kit)
- Elevated Base
- Sensor Mounting Bracket Assembly
- Communications Software Set
- OA Set Assembly
- Outdoor Wind Shield Assembly
- Base Cover Plate Set
- Remote Control Cord Assembly (20 m)
- Remote Control Cord Assembly (50 m)
- Remote Control Cord Assembly (100 m)
Applications
Application Examples
- Cleanroom (Pharmaceutical, Cosmetic Production Etc.)
- Precision Measurement Room (3-D Measurement Instruments, Tensile Testing Equipment, Laser Measurement Instruments, etc.)
- Precision Processing Room (Nano Processing Equipment, Electrical Discharge Machines, etc.)
- Storage of all kinds of Materials...etc.
- Plant Cultivation Room / Plant Factory...etc.
Every kind of system that meets our users demands.
System Installation Examples
① Outlet Control Method
② Intake Control Method
Installation Examples
Specifications
Temperature Control Type | ||||
---|---|---|---|---|
PAP20A-R | PAP40C-R | |||
Performance Specifications |
Possible Setting Range (Circulation Specifications) ※1 |
℃,% | 18 – 30 | |
Temperature Control Precision ※2,13 | ℃,% | ±0.2 | ||
Cooling Capacity (50/60 Hz) ※3 | kW | 8 | 12 | |
Heating Capacity (50/60 Hz) ※4 | kW | 3 | 5 | |
Rated Processing Airflow | m3/min | 20-23 | 40-45 | |
Maximum External Static Pressure(50/60 Hz) ※5 | Pa | 200 | ||
Environmental Conditions |
Indoor Unit Installation Temperature Conditions | ℃ | 5 – 35 | |
Outdoor Unit Installation Temperature Conditions | ℃ | -5 – 43 | ||
Temperature Gradient at Intake | ℃/h | Within ±2 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions |
Indoor Unit (HxDxW) ※6 | mm | 1800×555×980 | 1800×555×1100 |
Outdoor Unit (HxDxW) ※6 | mm | 824×420×810 | 1160×420×810 | |
Humidifier (HxDxW) ※6 | mm | - | ||
Product Mass | Indoor Unit | kg | 240 | 260 |
Outdoor Unit (H×D×W) | kg | 65 | 80 | |
Humidifier | kg | - | ||
Humidifier | Water Quality | Deionized water (electrical conductivity: 1 – 10 μS/cm) | ||
Humidification Capacity ※7 | kg/h | - | ||
Power Specific | Power Supply ※8 | V(Hz) | Three-phase 200 ± 10 % (50/60) | |
Power Consumption (50/60 Hz) (When Auxiliary Heater is Off) ※9 |
kW | 4.8 / 6.6 | 7.5 / 10.5 | |
Operating Current (50/60 Hz) (When Auxiliary Heater is Off) ※9 |
A | 18 / 23 | 31 / 40 | |
Power Supply Capacity ※10 | kVA | 8 | 14 | |
Sound Pressure Level | Indoor Unit (50/60 Hz) ※11 | dB | 68 or less | 69 or less |
Outdoor Unit (50/60 Hz) ※11 | dB | 59 or less | ||
Compressor Output | kW | 1.7 | 3.0 | |
Blower Fan | Indoor Unit ※12 | kW | 0.4 | |
Outdoor Unit ※12 | kW | 0.2 | 0.1×2 | |
Auxiliary Heater | kW | 1.8 | 3 | |
Refrigerant Piping Connections |
Gas Pipe | mm | Φ15.88 | |
Liquid Pipe | mm | Φ9.53 | ||
Refrigerant Piping | Max. Length (One Way) | m | 30 | 50 |
Max. Difference in Height | m | 10 | ||
Refrigerant | R410A | |||
High Pressure Gas Safety Act Classification | Not required |
Temperature Control Type | ||||
---|---|---|---|---|
PAP80B-R | PAP120A-R | |||
Performance Specifications |
Possible Setting Range (Circulation Specifications) ※1 |
℃,% | 18 – 30 | |
Temperature Control Precision ※2,13 | ℃,% | ±0.2 | ||
Cooling Capacity (50/60 Hz) ※3 | kW | 25 | 38 | |
Heating Capacity (50/60 Hz) ※4 | kW | 13 | 14.5 | |
Rated Processing Airflow | m3/min | 75 – 80 | 110 – 120 | |
Maximum External Static Pressure(50/60 Hz) ※5 | Pa | 400 | ||
Environmental Conditions |
Indoor Unit Installation Temperature Conditions | ℃ | 5 – 35 | |
Outdoor Unit Installation Temperature Conditions | ℃ | -5 – 43 | ||
Temperature Gradient at Intake | ℃/h | Within ±2 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions |
Indoor Unit (HxDxW) ※6 | mm | 1800×600×1500 | 1870×790×1900 |
Outdoor Unit (HxDxW) ※6 | mm | 1420×800×870 | 1420×800×870× 2units | |
Humidifier (HxDxW) ※6 | mm | - | ||
Product Mass | Indoor Unit | kg | 400 | 700 |
Outdoor Unit (H×D×W) | kg | 130 | 130×2 | |
Humidifier | kg | - | ||
Humidifier | Water Quality | Deionized water (electrical conductivity: 1 – 10 μS/cm) | ||
Humidification Capacity ※7 | kg/h | - | ||
Power Specific | Power Supply ※8 | V(Hz) | Three-phase 200 ± 10 % (50/60) | |
Power Consumption (50/60 Hz) (When Auxiliary Heater is Off) ※9 |
kW | 11 / 17 | 22.5 / 31.5 | |
Operating Current (50/60 Hz) (When Auxiliary Heater is Off) ※9 |
A | 42 / 60 | 93 / 122 | |
Power Supply Capacity ※10 | kVA | 23 | 40 | |
Sound Pressure Level | Indoor Unit (50/60 Hz) ※11 | dB | 69 or less | |
Outdoor Unit (50/60 Hz) ※11 | dB | 59 or less | ||
Compressor Output | kW | 4.6 | 7.5 | |
Blower Fan | Indoor Unit ※12 | kW | 2.2 | 3.75 |
Outdoor Unit ※12 | kW | 0.75 | 0.75×2 | |
Auxiliary Heater | kW | 6 | 9 | |
Refrigerant Piping Connections |
Gas Pipe | mm | Φ19.05 | Φ25.4 |
Liquid Pipe | mm | Φ12.70 | Φ15.88 | |
Refrigerant Piping | Max. Length (One Way) | m | 75 | |
Max. Difference in Height | m | 10 | ||
Refrigerant | R407C | |||
High Pressure Gas Safety Act Classification | Not required |
- The temperature and humidity control range noted does not necessarily indicate the actual controllable range possible. The range of control depends on the condition of the air supplied at the intake
- When the intake air temperature and humidity, and outdoor ambient temperature are stable. Noted precision is based on measurement by the internal controller at a single air outlet point.
- When operating according to JIS B 8616.The displayed performance will be at least 80% when the intake air temperature of the outdoor unit is at least 35 ˚C.
- When operating according to JIS B 8616.The displayed performance will be at least 75 % when the intake air temperature of the indoor unit is below 20 ˚C.The compressor will stop, and exclusive operation of the auxiliary heater may occur if the control air intake temperature drops to approx. 15 ˚C or lower.
- External dimensions do not include miscellaneous protrusions such as eyebolts, etc.
- Maximum value within the range of unit specifications. Starting current is equal to or less than the operating current.
- The noted external static pressure is when the controlled air is regulated at the outlet to produce the maximum rated processing air flow.
- Measured value (A scale) when operating at the rated processing air flow, at a position of non-resonance, 1 m from the front face of the indoor unit, and at 1 m from the front face of the outdoor unit, at a height of 1.5 m.
- The figure noted is when the equipment is operating at the highest level of humidification.operating at the highest capacity of its normal operating range.
- Noise level can be decreased by installing a noise reducing duct.
- Blower fan output cannot be increased.
- Use the measured temperature and humidity bias function to correct any error between the temperature and humidity shown on the control panel and the user's measured temperature and humidity.
- This product does not detect electrical shorts and does not have a protection function against them. An earth leakage breaker must be installed on the primary side of the power supply.
- All ducting should be insulated and ducting length should be kept as short as possible. (5 m or shorter recommended.)