PAP Water-Cooled Temperature Controlled Precision Air ProcessorCombining Energy Savings & High Precision! The Industry-Leading PAP Series

PAP05A1-W / PAP05A1-FW
PAP10C-WNEW/PAP10C-FWNEW
PAP20C-WNEW/PAP20C-FWNEW
PAP40B-W / PAP40B-FW

Air Processing Capacity
3 to 40 m3/min
Humidity Control Precision
±0.1℃
Temperature Setting Range
18 to 30℃

Special Order Product
Noise Reducing Intake Duct / Circulation Intake Chamber
Ventilation Air Out Chamber / Incl. Humidification Display

Table of Special Order Items Here

  • Please contact ORION regarding custom built models with specifications outside the ranges listed herein.
PAP Water-Cooled Temperature Controlled Precision Air Processor
PAP10C-W
supereco2
  • Intelligent Monitor
    Intelligent Monitor
  • Heat Pump Balance Control
    Heat Pump Balance Control
  • Capacity Control
    Capacity Control
  • HEPA Filter (F Type)
    HEPA Filter (F Type)
  • Air Cooled
    Air Cooled
  • Water Cooled
    Water Cooled
  • Temperature Control
    Temperature Control
  • Humidity Control
    Humidity Control

Specifications

PAP05A1-W PAP05A1-FW
Performance Possible Temperature Setting Range ※1 18 to 30
Temperature Control Precision ※2 ±0.1
Cooling + Heating Output (50/60 Hz) kW 3.2/3.2
(Maximum cooling capacity) (kW) (2.0)
Rated Processing Air Flow m3/min 3 to 5
Maximum External Static Pressure ※3 Pa 410/660 300/620
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ※1 ℃,% 15 to 35 , 30 to 70
Temperature Gradient at Intake ℃/h Within ±2
Humidity Gradient at Intake %/h Within ±5
Cooling Water Temp Gradient ℃/h Within ±5
External Dimensions (HxDxW) ※4 mm 1489×586×538
Product Mass kg 120 130
Controlled Air Outlet Port mm Φ100 Φ100
with built-in HEPA filter.
Cooling Water Rate of Supply ※6 m3/h 1.0
Supply Temp Range 15 to 32
Supply Pressure MPa 0.69 or lower
Inlet/Outlet Pressure Difference MPa 0.2 or higher
Connection Port Size Rc1/2
Electrical Specifications Power Source ※7 V(Hz) Three-phase 200 ±10% (50/60)
Power Consumption (50/60 Hz) ※8 kW 1.2/1.3
Electric Current ※8 A 4.5/5.2
Power Supply Capacity ※9 kVA 1.8
Noise Level (50/60 Hz) ※10 dB 68/71
Operation Control Method Heat Pump Balance Control
Refrigerant R410A
Chiller Compressor Output kW 0.7
PAP10C-W PAP10C-FW
Performance Possible Temperature Setting Range ※1 18 to 30
Temperature Control Precision ※2 ±0.1
Cooling + Heating Output (50/60 Hz) kW 6.5/6.5
(Maximum cooling capacity) (kW) (4.0)
Rated Processing Air Flow m3/min 7 to 10
Maximum External Static Pressure ※3 Pa 180 570
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ※1 ℃,% 15 to 35 , 30 to 70
Temperature Gradient at Intake ℃/h Within ±10
Humidity Gradient at Intake %/h Within ±5
Cooling Water Temp Gradient ℃/h Within ±5
External Dimensions (HxDxW) ※4 mm 1515×720×570 1855×720×570
Product Mass kg 163 205
Controlled Air Outlet Port mm Φ148 Φ148
with built-in HEPA filter box ※5
Cooling Water Rate of Supply ※6 m3/h 1.2
Supply Temp Range 15 to 32
Supply Pressure MPa 0.69 or lower
Inlet/Outlet Pressure Difference MPa 0.2 or higher
Connection Port Size Rc3/4
Electrical Specifications Power Source ※7 V(Hz) Three-phase 200 ±10% (50/60)
Power Consumption (50/60 Hz) ※8 kW 1.5
Electric Current ※8 A 4.6 4.8
Power Supply Capacity ※9 kVA 1.6 1.7
Noise Level (50/60 Hz) ※10 dB 64 73
Operation Control Method Heat Pump Balance Control
Refrigerant R32
Chiller Compressor Output kW 0.85
PAP20C-W PAP20C-FW
Performance Possible Temperature Setting Range ※1 18 to 30
Temperature Control Precision ※2 ±0.1
Cooling + Heating Output (50/60 Hz) kW 13.0/13.0
(Maximum cooling capacity) (kW) (8.0)
Rated Processing Air Flow m3/min 13 to 20
Maximum External Static Pressure ※3 Pa 110 540
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ※1 ℃,% 15 to 35 , 30 to 70
Temperature Gradient at Intake ℃/h Within ±10
Humidity Gradient at Intake %/h Within ±5
Cooling Water Temp Gradient ℃/h Within ±5
External Dimensions (HxDxW) ※4 mm 1515×860×640 1855×860×640
Product Mass kg 210 260
Controlled Air Outlet Port mm Φ198 Φ198
with built-in HEPA filter box ※5
Cooling Water Rate of Supply ※6 m3/h 2.2
Supply Temp Range 15 to 32
Supply Pressure MPa 0.69 or lower
Inlet/Outlet Pressure Difference MPa 0.2 or higher
Connection Port Size Rc3/4
Electrical Specifications Power Source ※7 V(Hz) Three-phase 200 ±10% (50/60)
Power Consumption (50/60 Hz) ※8 kW 3.1 3.0
Electric Current ※8 A 10.0 10.3
Power Supply Capacity ※9 kVA 3.5 3.6
Noise Level (50/60 Hz) ※10 dB 67 71
Operation Control Method Heat Pump Balance Control
Refrigerant R32
Chiller Compressor Output kW 1.85
PAP40B-W PAP40B-FW
Performance Possible Temperature Setting Range ※1 18 to 30
Temperature Control Precision ※2 ±0.1
Cooling + Heating Output (50/60 Hz) kW 22.0/22.0
(Maximum cooling capacity) (kW) (16.0)
Rated Processing Air Flow m3/min 25 to 40
Maximum External Static Pressure ※3 Pa 300/300 1000/1000
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ※1 ℃,% 15 to 35 , 30 to 70
Temperature Gradient at Intake ℃/h Within ±2
Humidity Gradient at Intake %/h Within ±5
Cooling Water Temp Gradient ℃/h Within ±5
External Dimensions (HxDxW) ※4 mm 1800×1200×900 2323×1200×900
Product Mass kg 440 540
Controlled Air Outlet Port mm Φ350 Φ350
with built-in HEPA filter box ※5
Cooling Water Rate of Supply ※6 m3/h 3.0
Supply Temp Range 15 to 32
Supply Pressure MPa 0.69 or lower
Inlet/Outlet Pressure Difference MPa 0.2 or higher
Connection Port Size Rc1
Electrical Specifications Power Source ※7 V(Hz) Three-phase 200 ±10% (50/60)
Power Consumption (50/60 Hz) ※8 kW 6.0
Electric Current ※8 A 24.0
Power Supply Capacity ※9 kVA 8.3
Noise Level (50/60 Hz) ※10 dB 75/75 83/83
Operation Control Method Heat Pump Balance Control
Refrigerant R410A
Chiller Compressor Output kW 3.0
  1. The temperature control range noted does not necessarily indicate the actual possible controllable range. The range of temperature control depends on the condition of the air supplied at the intake.
  2. Values indicated are for when the intake air temperature and humidity, and supply water temperature and flow rate are stable. Controller display precision at a single discharge port location.
  3. The external static pressure at the controlled air outlet side when operating at the maximum rated air flow.
  4. Height includes discharge port.
  5. The HEPA filter box is shipped separate from the product main unit and must be assembled on site.
  6. When operating at the maximum air flow and at the highest cooling capacity, and when the difference between the cooling water inlet and outlet ports is 6.5 ℃.
  7. The maximum allowable source voltage phase imbalance is ±3%.
  8. Maximum value within the range of the product's specifications.
  9. The figure noted is when operating at the highest capacity of the specified operating range.
  10. The noise level may be lowered by installing the Noise Reducing Duct.