PAP Air-Cooled Temperature and Humidity Controlled Precision Air ProcessorCombining Energy Savings & High Precision! The Industry-Leading PAP Series
PAP05A1-K / PAP05A1-FK
PAP10A1-K / PAP10A1-FK
PAP20A-K / PAP20A-FK
- Air Processing Capacity
- 3 to 20 m3/min
- Humidity Control Precision
- ±0.1℃
- Temperature Setting Range
- 18 to 30℃
- Humidity Control Precision
- ±1%
- Possible Humidity Setting Range
- 40 to 65%(75)※1
Special Order Product
Noise Reducing Intake Duct / Circulation Intake Chamber
Ventilation Air Out Chamber / Incl. Humidification Display
Table of Special Order Items Here
- Please contact ORION regarding custom built models with specifications outside the ranges listed herein.
Specifications
PAP05A1-K | PAP05A1-FK | |||
---|---|---|---|---|
Performance | Possible Temperature and Humidity Setting Ranges ※1 | ℃,% | 18 to 30,40 to 65(75) | |
Temperature and Humidity Control Precision ※2 | ℃,% | ±0.1,±1.0 | ||
Cooling + Heating Output (50/60 Hz) | kW | 2.3/2.6 | ||
(Maximum cooling capacity) | (kW) | (1.6)/(1.8) | ||
Rated Processing Air Flow | m3/min | 3 to 5 | ||
Maximum External Static Pressure ※3 | Pa | 110 | 620 | |
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) | ℃,% | 15 to 35,30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions (HxDxW) ※4 | mm | 1589×800×650 | 1810×800×650 | |
Product Mass | kg | (190) | (215) | |
Controlled Air Outlet Port | mm | Φ100 | Φ100 with built-in HEPA filter. |
|
Humidification Water | Water Quality | Deionized water (electrical conductivity:1-10 µS/cm) |
||
Maximum Humidification Output ※6 | kg/h | 2.5 | ||
Supply Temp Range | ℃ | 10 to 40 | ||
Supply Pressure Range | MPa | 0.1 to 0.5 | ||
Connection Port Size | Rc1/4 | |||
Humidification Air | Maximum Air Consumption ※7 | NL/min | 23 | |
Supply Temp Range | ℃ | 20 to 40 | ||
Supply Pressure Range | MPa | 0.40 to 0.93 | ||
Connection Port Size | Rc1/4 | |||
Electrical Specifications | Power Source ※8 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption ※9 | kW | 1.6 | ||
Electric Current ※9 | A | 6.6 | ||
Power Supply Capacity ※10 | kVA | 2.3 | ||
Noise Level (50/60 Hz) ※11 | dB | 68/68 | 73/73 | |
Operation Control Method | Heat Pump Balance Control | |||
Refrigerant | R410A | |||
Chiller Compressor Output | kW | 0.7 |
PAP10A1-K | PAP10A1-FK | |||
---|---|---|---|---|
Performance | Possible Temperature and Humidity Setting Ranges ※1 | ℃,% | 18 to 30,40 to 65(75) | |
Temperature and Humidity Control Precision ※2 | ℃,% | ±0.1,±1.0 | ||
Cooling + Heating Output (50/60 Hz) | kW | 4.7/5.3 | ||
(Maximum cooling capacity) | (kW) | (3.2)/(3.6) | ||
Rated Processing Air Flow | m3/min | 7 to 10 | ||
Maximum External Static Pressure ※3 | Pa | 250 | 560 | |
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) | ℃,% | 15 to 35,30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions (HxDxW) ※4 | mm | 1798×940×664 | 2203×940×664 | |
Product Mass | kg | (235) | (280) | |
Controlled Air Outlet Port | mm | Φ150 | Φ150 with built-in HEPA filter box ※5 |
|
Humidification Water | Water Quality | Conditioned water (with an electrical conductivity of 1 to 10 µS/cm) | ||
Maximum Humidification Output ※6 | kg/h | 5.0 | ||
Supply Temp Range | ℃ | 10 to 40 | ||
Supply Pressure Range | MPa | 0.1 to 0.5 | ||
Connection Port Size | Rc1/4 | |||
Humidification Air | Maximum Air Consumption ※7 | NL/min | 38 | |
Supply Temp Range | ℃ | 20 to 40 | ||
Supply Pressure Range | MPa | 0.40 to 0.93 | ||
Connection Port Size | Rc1/4 | |||
Electrical Specifications | Power Source ※8 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption ※9 | kW | 2.2 | ||
Electric Current ※9 | A | 8.0 | ||
Power Supply Capacity ※10 | kVA | 2.8 | ||
Noise Level (50/60 Hz) ※11 | dB | 70/70 | 75/75 | |
Operation Control Method | Heat Pump Balance Control | |||
Refrigerant | R410A | |||
Chiller Compressor Output | kW | 0.7 |
PAP20A-K | PAP20A-FK | |||
---|---|---|---|---|
Performance | Possible Temperature and Humidity Setting Ranges ※1 | ℃,% | 18 to 30,40 to 65(75) | |
Temperature and Humidity Control Precision ※2 | ℃,% | ±0.1,±1.0 | ||
Cooling + Heating Output (50/60 Hz) | kW | 9.4/10.5 | ||
(Maximum cooling capacity) | (kW) | (6.5)/(7.2) | ||
Rated Processing Air Flow | m3/min | 13 to 20 | ||
Maximum External Static Pressure ※3 | Pa | 250 | 690 | |
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) | ℃,% | 15 to 35,30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions (HxDxW) ※4 | mm | 1863×1150×820 | 2263×1150×820 | |
Product Mass | kg | (370) | (445) | |
Controlled Air Outlet Port | mm | Φ200 | Φ200 with built-in HEPA filter box ※5 |
|
Humidification Water | Water Quality | Conditioned water (with an electrical conductivity of 1 to 10 µS/cm) | ||
Maximum Humidification Output ※6 | kg/h | 10.0 | ||
Supply Temp Range | ℃ | 10 to 40 | ||
Supply Pressure Range | MPa | 0.1 to 0.5 | ||
Connection Port Size | Rc1/4 | |||
Humidification Air | Maximum Air Consumption ※7 | NL/min | 80 | |
Supply Temp Range | ℃ | 20 to 40 | ||
Supply Pressure Range | MPa | 0.40 to 0.93 | ||
Connection Port Size | Rc1/4 | |||
Electrical Specifications | Power Source ※8 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption ※9 | kW | 4.5 | ||
Electric Current ※9 | A | 16.0 | ||
Power Supply Capacity ※10 | kVA | 5.6 | ||
Noise Level (50/60 Hz) ※11 | dB | 72/72 | 78/78 | |
Operation Control Method | Heat Pump Balance Control | |||
Refrigerant | R410A | |||
Chiller Compressor Output | kW | 3.0 |
- The temperature and humidity control ranges noted do not necessarily indicate the actual possible controllable ranges. The actual controllable temperature and humidity ranges will depend on the temperature and humidity of the intake air.(Vapor humidification is used in the humidity setting range of 65 to 75%.)
- When the intake air temperature and humidity are stable. Controller display precision at a single discharge port location.
- The external static pressure at the controlled air outlet side when operating at the maximum rated processing air flow.
- Height includes discharge port.
- The HEPA filter box is shipped separate from the product main unit and must be assembled on site.
- The figure noted is when the product is operating at the highest level of humidification.
- Supply compressed air that has been cleaned through a filter and/or other by other means of processing. The cleanliness of the compressed air supply should match the air cleanliness standard of the target area to which the controlled air will be supplied.
- The maximum allowable source voltage phase imbalance is ±3%.
- Maximum value within the range of the product's specifications.
- The figure noted is when operating at the highest capacity of the specified operating range.
- The noise level may be lowered by installing the Noise Reducing Duct.