PAP Air-Cooled Temperature and Humidity Controlled Precision Air ProcessorCombining Energy Savings & High Precision! The Industry-Leading PAP Series

PAP05A1-K / PAP05A1-FK
PAP10A1-K / PAP10A1-FK
PAP20A-K / PAP20A-FK

Air Processing Capacity
3 to 20 m3/min
Humidity Control Precision
±0.1℃
Temperature Setting Range
18 to 30℃
Humidity Control Precision
±1%
Possible Humidity Setting Range
40 to 65%(75)※1

Special Order Product
Noise Reducing Intake Duct / Circulation Intake Chamber
Ventilation Air Out Chamber / Incl. Humidification Display

Table of Special Order Items Here

  • Please contact ORION regarding custom built models with specifications outside the ranges listed herein.
PAP Air-Cooled Temperature and Humidity Controlled Precision Air Processor
PAP10A1-K
supereco2
  • Intelligent Monitor
    Intelligent Monitor
  • Heat Pump Balance Control
    Heat Pump Balance Control
  • Capacity Control
    Capacity Control
  • HEPA Filter (F Type)
    HEPA Filter (F Type)
  • Air Cooled
    Air Cooled
  • Water Cooled
    Water Cooled
  • Temperature Control
    Temperature Control
  • Humidity Control
    Humidity Control

Specifications

PAP05A1-K PAP05A1-FK
Performance Possible Temperature and Humidity Setting Ranges ※1 ℃,% 18 to 30,40 to 65(75)
Temperature and Humidity Control Precision ※2 ℃,% ±0.1,±1.0
Cooling + Heating Output (50/60 Hz) kW 2.3/2.6
(Maximum cooling capacity) (kW) (1.6)/(1.8)
Rated Processing Air Flow m3/min 3 to 5
Maximum External Static Pressure ※3 Pa 110 620
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ℃,% 15 to 35,30 to 70
Temperature Gradient at Intake ℃/h Within ±1
Humidity Gradient at Intake %/h Within ±5
External Dimensions (HxDxW) ※4 mm 1589×800×650 1810×800×650
Product Mass kg (190) (215)
Controlled Air Outlet Port mm Φ100 Φ100
with built-in HEPA filter.
Humidification Water Water Quality Deionized water
(electrical conductivity:1-10 µS/cm)
Maximum Humidification Output ※6 kg/h 2.5
Supply Temp Range 10 to 40
Supply Pressure Range MPa 0.1 to 0.5
Connection Port Size Rc1/4
Humidification Air Maximum Air Consumption ※7 NL/min 23
Supply Temp Range 20 to 40
Supply Pressure Range MPa 0.40 to 0.93
Connection Port Size Rc1/4
Electrical Specifications Power Source ※8 V(Hz) Three-phase 200 ±10% (50/60)
Power Consumption ※9 kW 1.6
Electric Current ※9 A 6.6
Power Supply Capacity ※10 kVA 2.3
Noise Level (50/60 Hz) ※11 dB 68/68 73/73
Operation Control Method Heat Pump Balance Control
Refrigerant R410A
Chiller Compressor Output kW 0.7
PAP10A1-K PAP10A1-FK
Performance Possible Temperature and Humidity Setting Ranges ※1 ℃,% 18 to 30,40 to 65(75)
Temperature and Humidity Control Precision ※2 ℃,% ±0.1,±1.0
Cooling + Heating Output (50/60 Hz) kW 4.7/5.3
(Maximum cooling capacity) (kW) (3.2)/(3.6)
Rated Processing Air Flow m3/min 7 to 10
Maximum External Static Pressure ※3 Pa 250 560
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ℃,% 15 to 35,30 to 70
Temperature Gradient at Intake ℃/h Within ±1
Humidity Gradient at Intake %/h Within ±5
External Dimensions (HxDxW) ※4 mm 1798×940×664 2203×940×664
Product Mass kg (235) (280)
Controlled Air Outlet Port mm Φ150 Φ150
with built-in HEPA filter box ※5
Humidification Water Water Quality Conditioned water (with an electrical conductivity of 1 to 10 µS/cm)
Maximum Humidification Output ※6 kg/h 5.0
Supply Temp Range 10 to 40
Supply Pressure Range MPa 0.1 to 0.5
Connection Port Size Rc1/4
Humidification Air Maximum Air Consumption ※7 NL/min 38
Supply Temp Range 20 to 40
Supply Pressure Range MPa 0.40 to 0.93
Connection Port Size Rc1/4
Electrical Specifications Power Source ※8 V(Hz) Three-phase 200 ±10% (50/60)
Power Consumption ※9 kW 2.2
Electric Current ※9 A 8.0
Power Supply Capacity ※10 kVA 2.8
Noise Level (50/60 Hz) ※11 dB 70/70 75/75
Operation Control Method Heat Pump Balance Control
Refrigerant R410A
Chiller Compressor Output kW 0.7
PAP20A-K PAP20A-FK
Performance Possible Temperature and Humidity Setting Ranges ※1 ℃,% 18 to 30,40 to 65(75)
Temperature and Humidity Control Precision ※2 ℃,% ±0.1,±1.0
Cooling + Heating Output (50/60 Hz) kW 9.4/10.5
(Maximum cooling capacity) (kW) (6.5)/(7.2)
Rated Processing Air Flow m3/min 13 to 20
Maximum External Static Pressure ※3 Pa 250 690
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ℃,% 15 to 35,30 to 70
Temperature Gradient at Intake ℃/h Within ±1
Humidity Gradient at Intake %/h Within ±5
External Dimensions (HxDxW) ※4 mm 1863×1150×820 2263×1150×820
Product Mass kg (370) (445)
Controlled Air Outlet Port mm Φ200 Φ200
with built-in HEPA filter box ※5
Humidification Water Water Quality Conditioned water (with an electrical conductivity of 1 to 10 µS/cm)
Maximum Humidification Output ※6 kg/h 10.0
Supply Temp Range 10 to 40
Supply Pressure Range MPa 0.1 to 0.5
Connection Port Size Rc1/4
Humidification Air Maximum Air Consumption ※7 NL/min 80
Supply Temp Range 20 to 40
Supply Pressure Range MPa 0.40 to 0.93
Connection Port Size Rc1/4
Electrical Specifications Power Source ※8 V(Hz) Three-phase 200 ±10% (50/60)
Power Consumption ※9 kW 4.5
Electric Current ※9 A 16.0
Power Supply Capacity ※10 kVA 5.6
Noise Level (50/60 Hz) ※11 dB 72/72 78/78
Operation Control Method Heat Pump Balance Control
Refrigerant R410A
Chiller Compressor Output kW 3.0
  1. The temperature and humidity control ranges noted do not necessarily indicate the actual possible controllable ranges. The actual controllable temperature and humidity ranges will depend on the temperature and humidity of the intake air.(Vapor humidification is used in the humidity setting range of 65 to 75%.)
  2. When the intake air temperature and humidity are stable. Controller display precision at a single discharge port location.
  3. The external static pressure at the controlled air outlet side when operating at the maximum rated processing air flow.
  4. Height includes discharge port.
  5. The HEPA filter box is shipped separate from the product main unit and must be assembled on site.
  6. The figure noted is when the product is operating at the highest level of humidification.
  7. Supply compressed air that has been cleaned through a filter and/or other by other means of processing. The cleanliness of the compressed air supply should match the air cleanliness standard of the target area to which the controlled air will be supplied.
  8. The maximum allowable source voltage phase imbalance is ±3%.
  9. Maximum value within the range of the product's specifications.
  10. The figure noted is when operating at the highest capacity of the specified operating range.
  11. The noise level may be lowered by installing the Noise Reducing Duct.