PAP mini Air-Cooled Precision Air ProcessorDespite its compact design, delivers temperature and humidity controlled air for clean spaces while cutting energy consumption by as much as 80%!

PAP01B / PAP01B-KJ
PAP03C / PAP03C-KJ

Air Processing Capacity
0.7 to 4.0 m3/min
Humidity Control Precision
±0.1℃
Temperature Setting Range
18 to 30℃
Humidity Control Precision
±1% ※KJ models only
Possible Humidity Setting Range
45 to 75% ※KJ models only

Special Order Product
Noise Reducing Intake Duct / Circulation Intake Chamber
Ventilation Air Chamber / Compact Chamber Box

Table of Special Order Items Here

  • Please contact ORION regarding custom built models with specifications outside the ranges listed herein.
PAP mini Air-Cooled Precision Air Processor
PAP03C
supereco2
  • Intelligent Monitor
    Intelligent Monitor
  • Heat Pump Balance Control
    Heat Pump Balance Control
  • Capacity Control
    Capacity Control
  • HEPA Filter (F Type)
    HEPA Filter (F Type)
  • Air Cooled
    Air Cooled
  • Water Cooled
    Water Cooled
  • Temperature Control
    Temperature Control
  • Humidity Control (KJ Type)
    Humidity Control
    (KJ Type)

Specifications

PAP01B
(Temperature Control Type)
PAP01B-KJ
(Temperature and Humidity Control Type)
Performance Possible Temperature and Humidity Setting Ranges ※1 ℃,% 18 to 30 18 to 30,45 to 75
Temperature and Humidity Control Precision ※2 ℃,% ±0.1 ±0.1,±1.0
Cooling + Heating Output (50/60 Hz) ※3 kW 0.33/0.39 0.77/0.84
(Maximum cooling capacity) (kW) (0.22/0.26) (0.37/0.44)
Rated Processing Air Flow m3/min 0.7 to 1.0
Maximum External Static Pressure ※4 Pa 120/130 120/160
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ※1 ℃,% 15 to 35,30 to 70
Temperature Gradient at Intake ℃/h Within ±1
Humidity Gradient at Intake %/h Within ±5
External Dimensions (HxDxW) ※5 mm 346×500×412 765×620×390
Product Mass kg (32) (69)
Controlled Air Outlet Port mm Φ75 Φ100
Humidification Water Water Quality - Deionized water
(electrical conductivity:1-10 µS/cm)
Maximum Moisuture Output ※6 kg/h - 0.8
Supply Temperature Range - 10 to 40
Connection Port Size - Rc1/4
Electrical Specifications Power Supply ※7 ※10 V(Hz) Single-phase 100±10% (50/60)
Power Consumption kW 0.32/0.34 1.2/1.2
Electric Current ※8 A 4.0/3.9 13/13
Power Supply Capacity ※9 kVA 0.34/0.38 1.5/1.5
Noise Level (50/60 Hz) ※10 dB 54/56 58/60
Refrigerant R134a R407C
Compressor Output kW 0.25 0.3
  1. The temperature and humidity control ranges noted do not necessarily indicate the actual possible controllable ranges. The actual controllable temperature and humidity ranges will depend on the temperature and humidity of the intake air as well as process air flow rate. Set the processing air flow according to the operating environment.
  2. When the intake air temperature and humidity are stable. Noted precision value displayed on the controller is for one point at the outlet port. When operating at the maximum rated air flow.
  3. When the intake (surrounding) air temperature and humidity are 30 ℃, 70 %, at a processing air flow of 1 m3/min .
  4. The eternal static pressure at the controlled air outlet side of the blower fan outlet side when operating at the maximum rated processing air flow.
  5. Height includes the outlet port.
  6. The figure noted is when operating at the top of the specified level of humidification.
  7. Plug the product into a dedicated outlet in order to prevent voltage drops.
  8. Maximum value within the range of the product's specifications.
  9. When operating at the maximum operating current within the specified range.
  10. Includes a 2 m power cord.
  • Ducting should be insulated, and ducting length should be kept as short as possible. (Recommended maximum length: 3 m)
PAP03C
(Temperature Control Type)
PAP03C-KJ
(Temperature and Humidity Control Type)
Performance Possible Temperature and Humidity Setting Ranges ※1 ℃,% 18 to 30 18 to 30,45 to 75
Temperature and Humidity Control Precision ※2 ℃,% ±0.1 ±0.1,±1.0
Cooling + Heating Output (50/60 Hz) ※3 kW 1.65/1.85 1.8/2.12
(Maximum cooling capacity) (kW) (1.15/1.35) (1.2/1.42)
Rated Processing Air Flow※1 m3/min 2.0 to 4.0
Maximum External Static Pressure ※4 Pa 110/150 110/150
Environmental Conditions Ambient Temp and Humidity Range (Intake air) ※1 ※5 ℃,% 15 to 40,30 to 70
Temperature Gradient at Intake ℃/h Within ±1
Humidity Gradient at Intake %/h Within ±5
External Dimensions (HxDxW) ※6 mm 1070×590×480 1350×680×520
Product Mass kg (95) (135)
Controlled Air Outlet Port mm Φ98
Humidification Water Water Quality - Deionized water
(electrical conductivity:1-10 µS/cm)
Maximum Humidification Output ※7 kg/h - 2.3
Supply Temperature Range - 10 to 40
Connection Port Size - Rc1/4
Electrical Specifications Power Supply ※8 V(Hz) Three-phase 200 ±10% (50/60)
Power Consumption※9 kW 0.75/0.85 2.7/3.1
Electric Current ※10 A 3.8/3.8 11/12
Power Supply Capacity ※11 kVA 1.4 4.0
Noise Level (50/60 Hz) dB 64/65 65/66
Refrigerant R410A
Compressor Output kW 0.8 0.85
  1. The temperature and humidity control ranges noted do not necessarily indicate the actual possible controllable ranges. The actual controllable temperature and humidity ranges will depend on the temperature and humidity of the intake air as well as the process air flow rate. Set the processing air flow according to the operating environment.
  2. When the intake air temperature and humidity are stable. Noted precision value displayed on the controller is for one point at the outlet port. When operating at the rated processing air flow (3m³/min). After operation starts, for approx. 2 minutes the temperature will temporarily fluctuate due to operation while the compressor oil returns. Also, if the target humidity is high, and depending on the timing of the supply of the humidification water, the precision previously noted may not be able to be maintained. In such cases, by adjusting parameters related to supply water, the amount of fluctuation can be reduced.
  3. When the intake (surrounding) air temperature and humidity are 30 ℃, 70 %, at a processing air flow of 3 m³/min .
  4. When the processing air flow is 3 m³/min.
  5. See the operating manual for details regarding the possible operating range of ambient temperature and humidity.
  6. Height includes the outlet port.
  7. The figure noted is when operating at the top of the specified level of humidification.
  8. The source voltage phase unbalance should be less than ±3 %.
  9. The intake (surrounding) air temperature and humidity are 30 ℃, 70 %, at a processing air flow of 3 m3/min .
  10. Maximum value within the range of unit specifications.
  11. The figure noted is when the product is operating at the highest capacity of its normal operating range.
  • Ducting should be insulated, and ducting length should be kept as short as possible. (Recommended maximum length: 3 m)