PAP Air-Cooled Temperature Controlled Precision Air ProcessorCombining Energy Savings & High Precision! The Industry-Leading PAP Series
PAP05A1 / PAP05A1-F
PAP10A1 / PAP10A1-F
PAP20A / PAP20A-F
- Air Processing Capacity
- 3 to 20 m3/min
- Humidity Control Precision
- ±0.1℃
- Temperature Setting Range
- 18 to 30℃
Special Order Product
Noise Reducing Intake Duct / Circulation Intake Chamber
Ventilation Air Out Chamber / Incl. Humidification Display
Table of Special Order Items Here
- Please contact ORION regarding custom built models with specifications outside the ranges listed herein.
Specifications
PAP05A1 | PAP05A1-F | |||
---|---|---|---|---|
Performance | Possible Temperature Setting Range ※1 | ℃ | 18 to 30 | |
Temperature Control Precision ※2 | ℃ | ±0.1 | ||
Cooling + Heating Output (50/60 Hz) | kW | 2.3/2.6 | ||
(Maximum cooling capacity) | (kW) | (1.6)/(1.8) | ||
Rated Processing Air Flow | m3/min | 3 to 5 | ||
Maximum External Static Pressure ※3 | Pa | 110 | 620 | |
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) ※1 | ℃,% | 15 to 35,30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions (HxDxW) ※4 | mm | 1140×700×600 | 1423×700×600 | |
Product Mass | kg | (130) | (155) | |
Controlled Air Outlet Port | mm | Φ100 | Φ100 with built-in HEPA filter. |
|
Electrical Specifications | Power Source ※6 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption ※7 | kW | 1.4 | ||
Electric Current ※7 | A | 6.2 | ||
Power Supply Capacity ※8 | kVA | 2.2 | ||
Noise Level (50/60 Hz) ※9 | dB | 66/66 | 71/71 | |
Operation Control Method | Heat Pump Balance Control | |||
Refrigerant | R410A | |||
Chiller Compressor Output | kW | 0.7 |
PAP10A1 | PAP10A1-F | |||
---|---|---|---|---|
Performance | Possible Temperature Setting Range ※1 | ℃ | 18 to 30 | |
Temperature Control Precision ※2 | ℃ | ±0.1 | ||
Cooling + Heating Output (50/60 Hz) | kW | 4.7/5.3 | ||
(Maximum cooling capacity) | (kW) | (3.2)/(3.6) | ||
Rated Processing Air Flow | m3/min | 7 to 10 | ||
Maximum External Static Pressure ※3 | Pa | 250 | 560 | |
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) ※1 | ℃,% | 15 to 35,30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions (HxDxW) ※4 | mm | 1305×822×661 | 1565×822×661 | |
Product Mass | kg | (185) | (210) | |
Controlled Air Outlet Port | mm | Φ150 | Φ150 with built-in HEPA filter. |
|
Electrical Specifications | Power Source ※6 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption ※7 | kW | 1.8 | ||
Electric Current ※7 | A | 7.5 | ||
Power Supply Capacity ※8 | kVA | 2.6 | ||
Noise Level (50/60 Hz) ※9 | dB | 68/68 | 73/73 | |
Operation Control Method | Heat Pump Balance Control | |||
Refrigerant | R410A | |||
Chiller Compressor Output | kW | 1.7 |
PAP20A | PAP20A-F | |||
---|---|---|---|---|
Performance | Possible Temperature Setting Range ※1 | ℃ | 18 to 30 | |
Temperature Control Precision ※2 | ℃ | ±0.1 | ||
Cooling + Heating Output (50/60 Hz) | kW | 9.4/10.5 | ||
(Maximum cooling capacity) | (kW) | (6.5)/(7.2) | ||
Rated Processing Air Flow | m3/min | 13 to 20 | ||
Maximum External Static Pressure ※3 | Pa | 250 | 690 | |
Environmental Conditions | Ambient Temp and Humidity Range (Intake air) ※1 | ℃,% | 15 to 35,30 to 70 | |
Temperature Gradient at Intake | ℃/h | Within ±1 | ||
Humidity Gradient at Intake | %/h | Within ±5 | ||
External Dimensions (HxDxW) ※4 | mm | 1610×1150×770 | 2010×1150×770 | |
Product Mass | kg | (290) | (365) | |
Controlled Air Outlet Port | mm | Φ200 | Φ200 with built-in HEPA filter box ※5 |
|
Electrical Specifications | Power Source ※6 | V(Hz) | Three-phase 200 ±10% (50/60) | |
Power Consumption ※7 | kW | 3.9 | ||
Electric Current ※7 | A | 14.9 | ||
Power Supply Capacity ※8 | kVA | 5.2 | ||
Noise Level (50/60 Hz) ※9 | dB | 69/69 | 76/76 | |
Operation Control Method | Heat Pump Balance Control | |||
Refrigerant | R410A | |||
Chiller Compressor Output | kW | 3.0 |
- The temperature control range noted does not necessarily indicate the actual possible controllable range. The range of temperature control depends on the condition of the air supplied at the intake.
- When the intake air temperature and humidity are stable. Controller display precision at a single discharge port location.
- The external static pressure at the controlled air outlet side when operating at the maximum rated processing air flow.
- Height includes discharge port.
- The HEPA filter box is shipped separate from the product main unit and must be assembled on site.
- The maximum allowable source voltage phase imbalance is ±3%.
- Maximum value within the range of the product's specifications.
- The figure noted is when operating at the highest capacity of the specified operating range.
- The noise level may be lowered by installing the Noise Reducing Intake Duct.