Ultra-Low Dew Point Dry Air Supply Equipment Ultra low humidity space with a "one unit" design. Perfect for experimentation and research applications!

Precooler + Dehumidifier + After-Temperature Controller in a single unit. Offers an ultra-low humidity space with a "one unit" design. Precooler, desiccant dehumidifier, after-temperature controller all integrated into a single unit that will save valuable factory floor space. This single unit provides a stable supply of air with an ultra-low dew point.

超低露点ドライエアー供給装置
  • Ultra-low Dew Point
    Achieves a discharge dew point of –60 ℃.
  • Space Saving
    Precooler, dehumidifier, and after-temperature controller in a single unit.
  • High Precision Temperature Control (Supply Side)
    Temperature Control Precision: ±0.5 ℃
  • Energy Saving
    The dew point controller offers both low humidity and energy savings.
Ultra-Low Dew Point Dry Air Supply Equipment
DPU02A

Specifications

DPU02A
Performance SA (Supply Air) Dew Point ※1 -60 or lower
SA Set Temperature Setting Range 23 to 27
SA Temperature Precision ※2 ±0.5
Processing Air Flow m3/min 1.0 to 2.5
Environmental Conditions Outside Air Conditions ℃,% 15 to 30, 30 to 60
Temperature Gradient at Intake ℃/h Max. ±1
Humidity Gradient at Intake %/h Max. ±5
External Dimensions (H×D×W) mm 1850×1390×1050
Product Mass kg (500)
Controlled Air Outlet mm Φ98
Controlled Air Inlet mm Φ148
Regeneration Air Outlet mm Φ74
Electrical Specifications Power Supply Three-phase 200 V ±10%, 50/60 Hz
Power Consumption kW (6.3)
Current A (20)
Power Supply Capacity kVA (9.0)
Dehumidification Method Compressor + Desiccant Dehumidifier
Temperature Control Method Heat Pump Balance Control (Super Reheat Spec. Models)
  1. Capacity when under no load, and at a circulation of 2 m3/min.
  2. When the intake air temperature and humidity are stable. Controller display precision at a single discharge port location.
  • Dew point controlled by changing the desiccant rotor regeneration air temperature.