MG Dew Point MonitorEasy Temperature and Humidity Monitoring
MG40 (For Atmospheric-Pressure Air Applications) /
MG40A-P (For Compressed Air Applications)
- Humidity Display
-
0.1 to 99.9%, 1/10 Resolution (MG40)
0.1 to 50.0%, 1/10 Resolution (MG40A-P)
- Dew Point Display
-
–40.0 to +40.0 ℃, 1/10 Resolution
- –40.0 to –60.0 ℃ is for reference only.
- Temperature Display
- –20.0 to +80.0 ℃, 1/10 Resolution
This products is available for purchase online.
Features
- Simultaneous Display of Temperature and Humidity or Dew Point.(Can switch between humidity and dew point.)
- Comes Standard with Dew Point and Humidity Alarm Outputs(2 sets of non-voltage contacts)
- Comes Standard with Analog Outputs(Temperature, Humidity / Dew Point : DC Output)
Applications
- MG40
Indoor temperature, humidity, and dew point monitoring and management - MG40A-P
Compressed air temperature, and dew point monitoring and management
Specifications
| MG40※4 | MG40A-P※5 | ||||
|---|---|---|---|---|---|
| Main Unit Specifications | Humidity Display: 3-digit LED display | 0.1 to 99.9%, 1/10 resolution※1 | 0.1 to 50.0%, 1/10 resolution※1 | ||
| Displays "––––" on out of range, short circuit, or disconnect. | |||||
| Dew Point Display: 4-digit LED display (1 digit for symbol) |
–40.0 to +40.0 °C, 1/10 Resolution※1 ※2 (Displays "L" at –60 ℃ or lower, and "H" at +40 ℃ or higher) Values of –40 ℃ and below are for reference only. |
||||
| Temperature Display: 4-digit LED display (1 digit for symbol) |
–20.0 to +80.0 ℃, 1/10 Resolution (Displays "L" at –20 ℃ or lower, and "H" at +80 ℃ or higher. Displays "––––" on out of range, short circuit, or disconnect.) |
||||
| Operable Ambient Temperature Range | ℃ | 5 to 40 | |||
| Operable Ambient Temp Range | %RH | 0 to 85 (No condensation) | |||
| Storage Temp/Humidity Range | ℃ % | 5 to +55 / 45 to 85% | |||
| Power Supply | V | 100 Vac ±10% | |||
| Power Consumption | W | 20 | |||
| External Dimensions | Height | mm | 80 | ||
| Depth | mm | 220 | |||
| Width | mm | 260 | |||
| Piping Connection Size | mm | - | Φ4 (One-touch fitting) | ||
| Mass | kg | 2.7 | 2.9 | ||
| 外部出力 | Voltage Output | Dew Point: 0 to 5 Vdc (–60 to +40 ℃) | |||
| Humidity: 0 to 5 Vdc (0 to 100%) | Humidity: 0 to 2.5 Vdc (0 to 50%) | ||||
| Temperature: 0 to 5 Vdc (–20 to +80 ℃) | |||||
| Alarm Output | Dew Point (Upper/Lower Limit) / Humidity (Upper/Lower Limit) / Temperature (Upper/Lower Limit) No-voltage Contact Outputs (1a), 2 sets (AL1 and AL2) |
||||
| Sensor Specifications | Measurable Fluid | Pure air (at atmospheric pressure) / ISO purity class 8 (free of water droplets, oil, suspended organic solvents, etc.)※6 | Compressed air (free of water droplets, oil, dust. Always install a filter before this product.)※6 | ||
| Pressure Range | MPa | Atmospheric Pressure | 0.1 to 0.8 | ||
| Temperature Gauge Precision | ℃ | ±1 | |||
| Humidity Gauge Precision | %RH | ±2 (20 to 80%) at 25 ℃ | ±2 (20 to 40%) at 25 ℃ | ||
| Calculated Dew Point Precision | ℃ | ±3 for D.P. of –30 to +40 ℃ / ±5 for D.P. of –30 to –40 ℃※3 Values of –40 ℃ or lower are for reference only. (When the measured air temperature is 25 ℃.) |
|||
| Sampling Flow Rate | L/min | - | 3 to 5 Using a fixed orifice purge. | ||
- Pressing the display switch alternates display between humidity and dew point.
- The dew point is a calculated value based on temperature and humidity.
- The calculated dew point precision value at the time the product is shipped. This is not a guaranteed value.
- The MG40 is a dew point monitor intended for use with atmospheric pressure air. If taking a measurement, place the sensor directly in the air to be measured.
- The MG40A-P is a dew point monitor intended for use with compressed air. If taking measurements, then supply the air to be measured to the product via the included sampling air tube (Φ4, L2000).
- Using or storing in the following atmospheres will lead to deterioration of the sensor and necessitate recalibration in a short period of time:acetic acid, hydrochloric acid, ammonia, ethyl acetate, xylene, butanol, ethylene dichloride.