EDC60A Energy Saving Control UnitFor Remote Monitoring of Compressed Air Dew Point
EDC60A (Compatible with QSQ080B-E to QSQ2500C-E)
- Install after existing Super Pack units to achieve "Eco Pack" functionality.
- Energy saving control possible at arbitrary dew points of PDP –60 ℃ to 0 ℃.
- Comes standard with built-in dew point alarm output and analog output for possible remote monitoring of compressed air dew point.

Specifications
EDC60A | |||
---|---|---|---|
Operating Pressure Range | Operating Fluid※1 | Compressed air | |
Operating Pressure Range (Gauge pressure) | MPa | 0.39 to 0.988 | |
Ambient Temperature | ℃ | 2 to 40 | |
Ambient Humidity Range | % RH | 45 to 85 (No condensation) | |
Fluid Temperature Range | ℃ | 5 to 50 | |
Fluid Humidity Range | % RH | 0 to 100 (No condensation) | |
Dew Point Measurement Range | ℃ | -80 to 20 | |
Dew Point Control Range | ℃ | -60 to 0 | |
Sampling Flow Rate※2 ※3 | L/min | 3 to 5 (Using a fixed orifice purge) | |
Electrical Specifications | Power Source 50/60 Hz | V | Single-phase 100 to 230 Vac |
Input Power | W | 10 | |
Current (at 100 Vac) | mA | 100 | |
Main Dimensions | Main External Dimensions (H×D×W) |
mm | 89.5×202.5×226.5 |
Product Piping Connection Port Size | mm | Φ4 (One-touch pipe fitting) | |
Product Mass | kg | 3.0 | |
Storage Environment | Temperature Range | ℃ | -5 to 55 |
Humidity Range | % RH | 45 to 85 (No condensation) | |
Vibration Conditions | G | 0 to 0.5 | |
Function / Performance | Dew Point Display Range※4 | ℃ | –80 to 20 (1/10 resolution) |
Energy Saving Signal Output (Signal specifically for QSP and QSQ controllers.) |
No-voltage contacts output: 1a Contact rating: 250 V, 2 A Minimum applied load: 5 Vdc, 10 mA |
||
Alarm contact output※5 | No-voltage contacts output: 1a Contact rating: 250 V, 2 A Minimum applied load: 5 Vdc, 10 mA |
||
Analog Output | V | 1 to 5 Vdc (Dew point: –80 to 20 ℃) Minimum applied load: 10 KΩ or higher |
|
Sampling Period | sec | 0.5 | |
Dew Point Sensor Precision (Fluid temperature: 20 ℃)※6 ※7 ※8 |
℃ | ±3: Dew point of –60 to 20 Outside guaranteed precision: Dew point of –80 to –60 |
|
Responsiveness: 90% (Fluid temperature: 20 ℃) |
Dew point 10 → –40 ℃: 4 min |
- Sampled air that is adulterated with oil or water mist or dust can damage the product.
(Sampling air filtration quality: particulate filter degree: 0.3 µm or finer, oil concentration: 0.8 wt ppm or lower.) - Due to the fixed orifice, the flow rate of the sampling air does not have to be adjusted by the user.
- Always use a low water absorption fluorine tubing such as PTFE or PFA for the sampling air piping. (Included part: 3 m of fluorine tubing.)
- Displays dew point under operating pressure.
- There are 2 sets of alarm output contacts. (Operates with standby sequence.)
- The precision of displayed dew points of –80 to –60 ℃ are not guaranteed values and are for reference only.
- In order to assure precision, it is recommended that the dew point sensor be calibrated approx. every two years.
- Automatic Dew Point Sensor Cleaning Function: Note that new measurements will not occur during the sensor cleaning process, and during that time, the last measured value will be displayed. (The display will automatically return to normal after the cleaning process.)