RKS JM Compact Chiller With Water Tank (Air Cooled / Water Cooled)
High Precision Temperature Control + Inverter Driven
High Pressure Pump + High Ambient Temp Compatibility
- Cooling Capacity
(50/60Hz) - 1.3/1.5kW(RKS401/402J-MV)
1.8/2.0kW(RKS602J-MV)
2.2/2.5kW(RKS752/753J-MV)
4.9/5.3kW(RKS1502/1503J-MV)
- Operable
Ambient
Temperature - 5 - 45 ℃
- Working Liquid Temperature
- 5 - 40 ℃
- Temperature
Control Accuracy - ±0.1℃
- The electronic expansion valve control achieves ±0.1 ℃ high precision temperature control that translates to increased equipment production accuracy and quality.
- Our standard built-in high-pressure pump is inverter driven, thus achieving the same performance specifications even in regions that have different power frequencies.
- Wide Operable Ambient Temperature Range of 5 - 45 ℃. Working Liquid Temperature Range of 5 - 40 ℃ Supports Many Working Environments.
- CE and UL Targeted 4-Model Lineup
Three Single-Phase 200 to 230 V Power Model: RKS402J-MV, RKS602J-MV※, RKS752J-MV, and RKS1502J-MV.
The 4 models endling in -00000, -01000, and -11000 are CE and UL standards compliant. Models with other model numbers are available as with CE compliance via special order.- UL in progress for RKS602J-MV.
(Right) RKS1502/1503J-MV
Features
Made Even Easier to Use! Simple and Reassuring Design
Common on All RKS JM Series Models
Manufacturer Options
Manufacturer Options and Accessories(Sold Separately)
| ① Model | |
|---|---|
| 40 | 400 Class |
| 60 | 600 Class |
| 75 | 750 Class |
| 150 | 1500 Class |
| ② Power Source | |
|---|---|
| 1 | Single-Phase 100 V※1 |
| 2 | Single-Phase 200 ~ 230 V※2 |
| 3 | Three-Phase 200 V (50/60 Hz)※3 Three-Phase 220 V (60 Hz) |
| ③ Model | |
|---|---|
| M | Middle Grade Model |
| Blank | Economy Model |
| ④ Pump / Water Circuit | |
|---|---|
| 0 | Standard |
| 1 | High Head / High Flow-Rate※4 |
| 2 | Copper-free wetted parts |
| ⑤ Circuit Breaker | |
|---|---|
| 0 | Standard (NFB) |
| 1 | Earth leakage circuit breaker (ELB) |
| ⑥ External Surface | |
|---|---|
| 0 | Surface painted Steel sheet |
| 1 | Stainless Steel (SUS304) |
- 400 class only.
- J-MV Series only.
- 750 class and 1500 class only.
- RKS402J-MV, 602, and 750 class only.
Accessories (Sold Separately)
Many Functional Specifications Available to Match Your Application.
We have a page that shows all of our accessories. Have a look!
Application
We have a page that highlights applications of the RKS J(M) Series. Have a look!
- If a water cooled model is needed, then please order from the RKS-GM Series.
Specifications (Standard Products)
| Air Cooled | Water Cooled | |||||
|---|---|---|---|---|---|---|
| 401J-MV | 402J-MV | 402J-MVW | ||||
| Performance Specifications | Cooling Capacity (50/60 Hz)※1 | kW | 1.3/1.5 | |||
| Heating Capacity (50/60 Hz)※1 | kW | 0.53/0.53 | 0.38/0.42 | |||
| Ambient Temp. Range | ℃ | 5 - 45 | ||||
| Operating Temp. Range (Liquid Temp.) |
℃ | 5 - 40 | ||||
| Operating Water Pressure | MPa | 0.05 - 0.3 | ||||
| Control Precision※4 | ℃ | ±0.1 | ||||
| Min. Operating Circulation Rate (50/60 Hz) |
L/min | 10 (Head: 30 m) | ||||
| Power Specifications |
Power Source※2 | V(Hz) | Single-phase 100±10%(50/60) | Single-phase 200 - 230±10% (50/60) | ||
| Power Consumption (50/60 Hz)※1 | kW | 0.8/0.7 | 0.9/1.0 | 0.6/0.6 | ||
| Electric Current (50/60 Hz)※1 | A | 7.9/7.3 | 3.8/4.7 | 3.2/3.0 | ||
| Power Capacity※3 | kVA | 1.2 | 1.5 | 1.3 | ||
| Breaker Capacity※5 | A | 15 | 10 | |||
| Operation Control Method | Electronic expansion valve capacity control | |||||
| Equipment Details |
Compressor | kW | Hermetically sealed rotary type | |||
| 0.55 | 0.6 | |||||
| Condenser | Corrugated fin and tube parallel flow type | Plate type heat exchanger | ||||
| Evaporator | Construction | Plate type heat exchanger | ||||
| Material | SUS316 (Brazing: Cu) | |||||
| Discharge Pump | Construction | Cascade type | ||||
| Output | kW | 0.25 (Inverter driven) | ||||
| Water Tank Capacity | L | Approx. 17 | ||||
| Refrigerant | R410A | |||||
| Charge Amount | kg | 0.36 | 0.45 | |||
| External Dimensions (HxDxW) | mm | 615×500×375 | ||||
| Product Mass (Dry weight) | kg | 42 | 44 | |||
| Export Standards CE and UL (60 Hz only) | - | ○ | - | |||
| Operating Noise Level (50/60 Hz)※6 | dB | 59/62 | 59/60 | 54/55 | ||
| Air Cooled | ||||||
|---|---|---|---|---|---|---|
| 602J-MV | 752J-MV | 753J-MV | ||||
| Performance Specifications | Cooling Capacity (50/60 Hz)※1 | kW | 1.8/2.0 | 2.2/2.5 | ||
| Heating Capacity (50/60 Hz)※1 | kW | 0.6/0.6 | ||||
| Ambient Temp. Range | ℃ | 5 - 45 | ||||
| Operating Temp. Range (Liquid temp) | ℃ | 5 - 40 | ||||
| Operating Water Pressure | MPa | 0.05 - 0.3 | ||||
| Control Precision※4 | ℃ | ±0.1 | ||||
| Min. Operating Circulation Rate | L/min | 10 (Head: 30 m) | ||||
| Performance Specifications |
Power Source※2 | V(Hz) | Single-phase 200 - 230±10% (50/60) | Three-phase 200±10% (50/60) / 220±10% (60) | ||
| Power Consumption (50/60 Hz)※1 | kW | 1.0/1.1 | 1.1/1.2 | 0.9/1.0, 1.0 | ||
| Electric Current (50/60 Hz)※1 | A | 4.9/5.2 | 5.2/5.4 | 3.6/3.4, 3.4 | ||
| Power Capacity※3 | kVA | 2.0 | ||||
| Breaker Capacity※5 | A | 15 | 10 | |||
| Operation Control Method | Electronic expansion valve capacity control | |||||
| Equipment Details |
Compressor | kW | Hermetically sealed rotary type | |||
| 0.75 | 0.85 | |||||
| Condenser | Corrugated fin and tube parallel flow type | |||||
| Evaporator | Construction | Plate type heat exchanger | ||||
| Material | SUS316 (Brazing: Cu) | |||||
| Discharge Pump | Construction | Cascade type | ||||
| Output | kW | 0.25 (Inverter driven) | ||||
| Water Tank Capacity | L | Approx. 17 | ||||
| Refrigerant | R410A | |||||
| Charge Amount | kg | 0.37 | ||||
| External Dimensions (HxDxW) | mm | 615×500×375 | ||||
| Product Mass (Dry mass) | kg | 45 | 46 | |||
| Export Standards CE and UL (60 Hz only) | ○ | ○ (UL in progess) |
- | |||
| Operating Noise Level (50/60 Hz)※6 | dB | 61/62 | 62/63 | |||
| Air Cooled | ||||||
|---|---|---|---|---|---|---|
| 1502J-MV | 1503J-MV | |||||
| Performance Specifications |
Cooling Capacity (50/60 Hz)※1 | kW | 4.9/5.3 | |||
| Heating Capacity (50/60 Hz)※1 | kW | 1.1/1.1 | ||||
| Ambient Temp. Range | ℃ | 5 - 45 | ||||
| Operating Temp. Range (Liquid temp) | ℃ | 5 - 40 | ||||
| Operating Water Pressure | MPa | 0.1 - 0.6 | ||||
| Control Precision※4 | ℃ | ±0.1 | ||||
| Min. Operating Circulation Rate (50/60 Hz) |
L/min | 18 (Head: 60 m) | ||||
| Electrical Specifications |
Power Specifications※2 | V(Hz) | Single-phase 200 - 230 -5%+10% (50/60) | Three-phase 200±10% (50/60) / 220±10% (60) | ||
| Power Consumption (50/60 Hz)※1 | kW | 2.0/2.5 | 1.8/2.2, 2.2 | |||
| Electric Current (50/60 Hz)※1 | A | 9.5/11.3 | 6.6/8.2, 8.2 | |||
| Power Capacity※3 | kVA | 4.2 | ||||
| Breaker Capacity※5 | A | 30 | 15 | |||
| Operation Control Method | Electronic expansion valve capacity control | |||||
| Equipment Details |
Compressor | kW | Hermetically sealed rotary type | |||
| 1.2 | 1.8 | |||||
| Condenser | Corrugated fin and tube parallel flow type | |||||
| Evaporator | Construction | Plate type heat exchanger | ||||
| Material | SUS316 (Brazing: Cu) | |||||
| Discharge Pump | Construction | Cascade type | ||||
| Output | kW | 0.4 (Inverter driven) | ||||
| Water Tank Capacity | L | Approx. 17 | ||||
| Refrigerant | R410A | |||||
| Charge Amount | kg | 0.65 | 0.59 | |||
| External Dimensions (HxDxW) | mm | 933×590×375 | ||||
| Produvt Mass (Dry mass) | kg | 72 | 68 | |||
| Export Standards CE and UL (60 Hz only) | ○ | - | ||||
| Operating Noise Level (50/60 Hz)※6 | dB | 64/65 | 65/66 | |||
- Under the following conditions: Chilled water temp: 20 ℃, Ambient temp: 25 ℃, Max. discharge pump circulating load. Cooling capacity is at least 95% of listed figures. Heating capacity will change according to operating conditions.
- Source voltage phase unbalance should be less than ±3%.
- The figure noted is when the product is operating at its maximum rated capacity.
- When the current load is continuously within ±10%, and the ambient temperature is stable. However does not include starting times or when the heat-load exceeds the chiller capacity.
- Comes standard with a built-in overload protection circuit breaker (NFB).
- Operating noise levels are from a position of 1 m in front of the product and at a height of 1m.
- Do not use aluminum parts that will be wetted with the chilled water. Electronic corrosion of aluminum can cause clogging in the heat exchanger.
- Heat output from the unit (in kW) is approx. 1.3 times that of the cooling capacity.
- Depending on the operating environment, condensation may form on piping inside the product, and temporary leakage of water from the pump mechanical seals may also occur, therefore a drain pan should be installed if required.