FCC Free Cooling Chiller
Eco Hybrid (Air Cooled)
Maximum utilization of outside air. Offers significant power savings by reducing yearly power consumption

FCC15B [For Outdoor Installations]

Cooling Capacity
(50/60Hz)
37kW
Operable Ambient Temperature Range
-20 to 45℃
Operable Liquid Temperature Range
5 to 35℃
Temp Control Precision
±1.0℃
  • Significant Energy Savings Through Maximum Utilization of Natural Energy
  • Can be used in environments down to –20 °C.
  • As a modular chiller, up to 10 units (150 hp) can be connected in a single installation.
FCC15B
FCC15B
  • "ORION Eco Hybrid" is a registered trademark of Orion Machinery Co., Ltd.
Free cooling makes wide ranging savings to yearly power consumption.

Under Japanese climate, outside air is cool during winter and inter-seasonal periods. During these times, free cooling provides a primary source of cooling. This results in significant power savings for the year.

Comparison of Power Consumption Between FCC15B and Constant-Speed Chillers
Significant Energy Savings Through Maximum Utilization of Natural Energy!

Winter months have lower-temperature ambient air, so cooling can occur through free cooling alone. During inter-seasonal periods when the outside air temperature and Eco Hybrid output water temperature are about the same, free cooling can provide the primary source of cooling and the chiller can be utilized as needed when the cooling capacity of free cooling is lacking. Actively taking advantage of free cooling reduces power consumption and therefore saves energy.

Basic Operating Region
Basic Operating Region
3 Operation Modes in Response to the Outside Air Temperature
3 Operation Modes in Response to the Outside Air Temperature

Automatic switching between 3 operating modes in response to the outside air temperature. The outside air is utilized to the maximum extent in order to reduce power consumption.

Energy Saving Calculation Example
Energy Saving Calculation Example
FCC Operation Conditions (Visualization)
FCC Operation Conditions

* Energy saving value is a calculated estimate based on the yearly temperature data for 2016.The value can vary considerably based on actual yearly temperatures and the user's specific operating environment, and therefore should be used for reference only.
* Japanese Meteorological Agency Data. (http://www.data.jma.go.jp/obd/stats/etrn/index.php)

Energy Savings Calculation Based on User's Operating Environment and Conditions

Please contact us when thinking about chiller performance and energy savings!
Please fill in the items about operating conditions inside the red box and pass along the information to us.

  • Comparison targets will be Orion Inverter Chillers.
  • For comparisons with chillers from other makers, please inform us of the rated cooling capacity and rated power consumption of the models in question.
Units can be connected together for modular chiller operation. Up to 10 units can be connected. (150 hp)

Supports water tank pressure equalization for multi-unit operation thanks to our water tank pressure equalization piping configuration.
(On-site installation of pressure equalization piping is required. Please consult your ORION representative for details.)

Up to 10 units can be connected.
Modular connectability supports high loads and future expansion.

Increased user load demands can be met in 37 kW increments. Expansion requirements can be met at minimal cost.
※ Rating cooling capacity.

Modular connectability supports high loads and future expansion.

The FCC15B has 4-inch water tank pressure equalization piping ports. When connecting 2 or more units, these pressure equalization piping ports are connected to 4-inch or larger pipes in order to achieve balanced water levels among the water tanks.

Run/Stop operations for up to 20 units are possible from the Central Chiller Controller!

The Central Chiller Controller can even offer individual control for up to 20 units installed in groups of different chilled water systems.

Central Chiller Controller
Modular connectability supports high loads and future expansion.

The FCC15B has 4-inch water tank pressure equalization piping ports. When connecting 2 or more units, these pressure equalization piping ports are connected to 4-inch or larger pipes in order to achieve balanced water levels among the water tanks.

Central Chiller Controller
Robust Specifications that Support Outdoor Installations
Wide Operable Ambient Temp Range of 20 to 45 °C

The free cooling system employs a brine intermediate cooling method that allows the product to be used even in colder regions.

* External chilled water piping must be insulated. Also, please operate the product with the "Freeze Prevention Mode" enabled.- If the power supply is to be cut off and the product is to be put in storage, be sure to drain the water from the product's internal chilled water circuit as well as the external chilled water piping external to the product.

Liquid Temperature Range: 5 to 35 °C

Can be used for many applications.

Powder Coating

Powder coating of external surfaces offers improved corrosion-resistance.

Chiller Protection for Cold or Snowy Regions

Operate with confidence in cold climates or in areas that receive snowfall.

Snow Protection Hood (Optional equipment)

For outdoor installations in areas of falling snow, there is a danger of breakdown due to water ingress from snow that has fallen on the product and melted. Installation of the Snow Protection Hood can ensure reliable operation even in outdoor installations in regions that receive snowfall.
Part No. 03110847010

Wind Protection Panel (Optional equipment)

Prevents damage from foreign material being blown onto the outdoor-air heat exchanger during strong winds, and also used to prevent super-cooling during times of strong winds in cold-climate regions.
Part No. 03110846010 (one side) / 03110846020 (two sides)

Applications

The following page shows application examples of the our Free Cooling Chillers.
Have a look!

Specifications

Model FCC15B
Performance Cooling Capacity ※1 kW 37
Operable Ambient Temperature Range ※7※8 -20 to 45
Liquid Temp Setting Range 5 to 35
Control Precision ※4 ±1.0℃
Electrical Specifications Power Source ※2 V(Hz) Three-phase 200±10% (50/60), 220±10% (60)
Power Consumption ※1 kW 14.4
Electric Current ※1 A 47
Power Capacity ※3 kVA 19.5
Equipment Specifications Chiller Compressor Output kW 7.46 (Inverter drive)
Condenser (For refrigerant) Fin and tube forced air cooling
Evaporator (Fan cooler heat exchanger) Fin and tube forced air cooling
Evaporator Construction/Materials Plate type heat exchanger / SUS316 stainless steel (brazing: copper)
Discharge Pump Output kW 2.10 (Inverter drive)
Circulation Pump Output kW 1.26 (Inverter drive)
Fan Motor Output kW 2.00 (Inverter drive)
Refrigerant R410A
Water Tank Capacity ※5 L Approx. 60
External Dimensions (HxDxW) mm 2392×1100×1300
Product Mass (Water tank empty) kg 680
Operating Noise dB(A) 69
  1. Operation under the following conditions: chilled water temp: 20 °C, ambient temp: 32 °C, chilled water pressure: 0.5 MPa, chilled water flow rate at the minimum operating flow rate. Cooling capacity is –5% of the noted value or better.
  2. The source voltage phase unbalance should be within ±3%.
  3. The figure noted is when the product is operating at its maximum rated capacity.
  4. When the continuous current load fluctuation is within ±10%, the ambient temperature and power source, etc. are stable, and the chilled fluid flow is at least 80 L/min. However note that the following cases are excluded:Mode 3 (during free cooling) = ±2.0 °C
    ① Within 4 minutes after the compressor has started. (Temperature control will start 4 minutes after the compressor has started.)
    ② When the cooling load is small and the compressor is simply cycling ON and OFF, or when the thermal expansion valve goes from fully closed to open, or from open to fully closed.
    ③ When the load fluctuation is ±10% or greater of the current load, or when the mode is changed. At such times, the value will be ±3.0 °C.
    ④ When the water temperature setting is changed.
  5. When the liquid level gauge is at "F".
  6. The product water pressure is the water pressure at the water outlet of the product. Also, the total head of the discharge pump indicates the head at the chilled water outlet because it includes the internal head loss of the product.
  7. Also indicates the product storage temperature.
  8. When the chilled water circuit is not frozen.
  • None of the optional items are included but are available for purchase separately. Please order such items on an as-needed basis.