RKS Unit Cooler (Air Cooled / Water Cooled)
RKS250F1-S / RKS400F-S / RKS400F1 /
RKS500F / RKS750F / RKS1500F / RKS750F-W
- Cooling Capacity
(50/60Hz) - 0.59/0.62 to 4.30/4.65 kW
- Operable Ambient Temperature Range
- 5 to 40 ℃
- Operating Temperature Range
- 5 to 25℃
Features
Built with a heat exchanging coil that inhibits clogging and can be disassembled when required.
Chillers that use external water tanks are susceptible to foreign substances entering the system. With Orion's distinctive heat exchange coil system, there is less likelihood of clogging and yet, in the unlikely chance that clogging does occur, the coil can be removed for cleaning.
Connections and controls are focused onto the front panel for improved ease of use.
Our improved layout has operating switches, temperature display, IN/OUT water piping, and drain port, all accessible on the front panel.
Works well in space saving, low profile environments.
The height of the chiller has been lowered as much as possible allowing convenient placement in most site layouts.
Applications
The following page shows application examples of the Unit Cooler. Have a look!
Specifications
Air Cooled | ||||||
---|---|---|---|---|---|---|
RKS250F1-S | RKS400F-S | RKS400F1 | ||||
Performance Specifications |
Cooling Capacity (50/60Hz)※1 ※2 |
kW | 0.59/0.62 | 0.89/1.02 | ||
Operable Ambient Temperature Range |
℃ | 5 to 40 | ||||
Operating Liquid Temperature Range |
℃ | 5 to 25 | ||||
Power Specifications |
Power Source | V(Hz) | Single - phase 100±10% (50/60) |
Three - phase 200±10% (50/60) |
||
Power Consumption (50/60Hz)※2 |
kW | 0.34/0.39 | 0.42/0.49 | 0.45/0.50 | ||
Electric Current (50/60Hz)※2 |
A | 4.3/4.0 | 4.8/5.1 | 1.85/1.75 | ||
Power Capacity | kVA | 0.6 | 0.7 | 0.8 | ||
Breaker Capacity | A | 10 | 5 | |||
Equipment Details |
Compressor Output | kW | 0.4 | 0.3 | 0.5 | |
Condenser | Fin and tube forced air cooling | |||||
Heat Exchanger |
Construction | Shell and coil | ||||
Material | Shell:ABS Coil:SUS304 | |||||
Circulation Pump (50/60Hz) |
Output | W | 20 | |||
Circulating Rate |
L/min | 15 to 24 / 15 to 27 | ||||
Fan Motor Output※3 | W | 10 | ||||
Refrigerant | R134A | R407C | R410A | |||
Charged Amount | kg | 0.23 | 0.28 | 0.3 | ||
External Dimensions (H×D×W) | mm | 283×375×454 | 295×375×454 | |||
Unit Mass (dry weight) | kg | Approx. 25 | Approx. 30 | |||
Operating Noise Level (50/60Hz) ※4 | dB | 53/57 | ||||
Required Water Tank Capacity | L | 10 or more | 20 or more |
Air Cooled | ||||||
---|---|---|---|---|---|---|
RKS500F | RKS750F | RKS1500F | ||||
Performance Specifications |
Cooling Capacity (50/60Hz)※1 ※2 |
kW | 1.3/1.4 | 2.00/2.20 | 4.30/4.65 | |
Operable Ambient Temperature Range |
℃ | 5 to 40 | ||||
Operating Liquid Temperature Range |
℃ | 5 to 25 | ||||
Power Specifications |
Power Source | V(Hz) | Three - phase 200±10%(50/60) | Three - sphase 200±10%(50/60) 220±10%(60) |
||
Power Consumption (50/60Hz)※2 |
kW | 0.72/0.85 | 0.85/1.05 | 1.6/2.1、2.1※5 | ||
Electric Current (50/60Hz)※2 |
A | 3.0/2.8 | 3.2/3.6 | 6.0/7.0、6.9※5 | ||
Power Capacity | kVA | 1.3 | 1.6 | 3.5 | ||
Breaker Capacity | A | 5 | 10 | 15 | ||
Equipment Details |
Compressor Output | kW | 0.6 | 0.65 | 1.4 | |
Condenser | Fin and tube forced air cooling | |||||
Heat Exchanger |
Construction | Shell and coil | ||||
Material | Shell:ABS Coil:SUS304 | Shell:PBT Coil:SUS304 |
||||
Circulation Pump (50/60 Hz) |
Output | W | 20 | 45 | 85/150 | |
Circulating Rate |
L/min | 15 to 24 / 15 to 27 | 20 to 27 / 20 to 30 | 30 to 50 / 30 to 60 | ||
Fan Motor Output※3 | Wn | 10 | 25 | 100 | ||
Refrigerant | R407C | |||||
Charged Amount | kg | 0.28 | 0.36 | 0.95 | ||
External Dimensions (H×D×W) | mm | 333×375×484 | 398×405×534 | 600×500×650 | ||
Unit Mass (dry weight) | kg | Approx. 35 | Approx. 43 | Approx. 70 | ||
Operating Noise Level (50/60Hz)※4 | dB | 53/57 | 55/59 | 57/59 | ||
Req. Water Tank Capacity | L | 25 or more | 35 or more | 60 or more |
Water Cooled | ||||
---|---|---|---|---|
RKS750F-W | ||||
Performance Specification |
Cooling Capacity (50/60Hz)※1 ※2 |
kW | 1.98/2.21 | |
Operable Ambient Temperature Range |
℃ | 5 to 40 | ||
Operating Liquid Temperature Range |
℃ | 5 to 25 | ||
Power Specifications |
Power Source | V(Hz) | Three-phase 200±10%(50/60) | |
Power Consumption (50/60Hz)※2 |
kW | 0.73/0.89 | ||
Electric Current (50/60 Hz)※2 |
A | 2.7/3.0 | ||
Power Capacity | kVA | 1.2 | ||
Breaker Capacity | A | 5 | ||
Equipment Details |
Compressor Output | kW | 0.65 | |
Condenser | Double-pipe water cooling | |||
Heat Exchange |
Construction | Shell and coil | ||
Material | Shell:ABS Coil:SUS304 | |||
Circulation Pump (50/60Hz) |
Output | W | 45 | |
Circulating Rate |
L/min | 20 to 27 / 20 to 30 | ||
Fan Motor Output※3 | W | - | ||
Refrigerant | R407C | |||
Chaged Amount | kg | 0.33 | ||
External Dimensions (H×D×W) | mm | 398×405×534 | ||
Unit Mass (dry weight) | kg | Approx. 45 | ||
Operating Noise Level (50/60 Hz)※4 | dB | 51/55 | ||
Req. Water Tank Capacity | L | 35 or more |
- Cooling capacity is at least 95% of listed figures.
- When liquid temperature 20℃ and ambient temperature is 32℃.
- Fan motor static pressure is 20Pa.
- Operating noise levels are from a position of 1m in front of the unit and at a height of 1m.
- At 200V 50/60Hz or 220V 60Hz.
- The recommended liquid (chilled water) that can be used is either clean water or a 30-40% industrial-use ethylene glycol solution. Aiternatively, if deionized water is used, it should have an electrical conductivity of at least 1µS/cm.
- Heat output the equipment (in kW) is about 1.3 times the cooling capacity. (air cooled models only)
- RKS750F-W is a built to order item.