Accessories (RKE Compact DC Models)

Equipment List

Model Name (RKE Series) Column Notation Key

 - 
Not Supported
On-site Installed Option (Part number will differ depending on product model. Please ask for details.)
Manufacturer Optional Item
凡例用
Click for relevant cautions.
凡例用
Click for further information.
Equipment List

画像をタップすることで拡大表示されます。

Equipment List
Function List Model Name (RKE Series)
Corresponding Item Comments 7
5
0
A
1
|
V
1
5
0
0
B
1
|
V
2
2
0
0
B
1
|
V
1
5
0
0
B
1
|
V
W
2
2
0
0
B
1
|
V
W
Operating Environment Nybrine (Z-1) 30 to 40% Solution※3    
30 to 40% ethylene glycol solution ※3  
Deionized (Conditioned) Water, Electrical Conductivity: 1 µS/cm or Higher Copperless Spec. Wetted Parts ※4  
Working Liquid (Chilled Water) Temp 5 to 35 ℃    
0 to 35 ℃ Use a 40% ethyl glycol solution. <sup>※4</sup>  
Freeze-Prevention Mode This function operates the discharge pump in order to prevent drops in water temperature and freezing during winter months when the product is not otherwise operating.
When enabled, the discharge pump will operate when the water temperature falls to 3 ℃ or below.
Can be enabled or disabled via the operation panel. ※ Cannot be used at the same time as the Warm Up Mode.  
Warm Up Mode This function will automatically operate the discharge pump at times when the product is otherwise not operating when the ambient temperature is low, for example during winter months, in order to prevent the water temperature from dropping too much and in order to help maintain the set water temperature. When this mode is enabled, the water temperature can be set within the temperature range of 10 to 35 ℃ as desired. Can be enabled or disabled via the operation panel. ※ Cannot be used at the same time as the Freeze-Prevention mode.  
Low Noise Mode This function will limit the upper speed of the fan, thus reducing the fan ventilation noise. ※4 Can be set to  
Cleanroom (Leakage Alarm Spec.) In addition to the standard specification, leak-detect spec. models include leak-detection functionality (leakage sensor and leakage detection unit) built in. Pressure resistant piping, insulated refrigeration, piping, insulated water piping standard. (For models specified with leak detection specifications.)    
Water Leakage Detection The standard specification includes leak-detection functionality (leakage sensor and leakage detection unit) built in.    
Vibration Reducing Base Reduces transmission of vibration from the chiller.    
Chilled Water Circuit Discharge Pump Specs. ※1 High-Head Pump [A] 必要な流量及び圧力を指定ください。        
High-Head Pump [B] High-head (0.5 to 0.6 MPa) pump compatible (At 0.6 MPa: 750,1500: 14/18 L/min, 2200: 25/31 L/min) The cooling capacity will be reduced by the amount of heat generated by the pump. Reduction amount by model – 750: 0.5 kW; 1500: 0.35 kW; 2200: 0.75 kW.  
Relief Valve (Pressure Valve) Can provide equipment-side pressure protection. Pressure valve: Set to 0.3 to 0.5 MPa. (If exceeding 0.5 MPa, please consult us each time regarding the pressure resistance of the product and the built in pump.)
Water Tank Water-Level Alarm
(Lower limit alarm)
Used to avoid water shortages due to evaporation.    
Automatic Water Supply A ball tap is provided in the water tank in order to maintain a uniform water level. The special ball tap is installed on-site. (There is no ball tap included on the supply port on the main unit. <sup>※2</sup>)  
Shipped with ball tap pre-installed.    
Chilled Water Inlet/Outlet Open/Close Gate valves are added to the chilled water inlet and outlet ports. Gate Valve: Same port diameter as the product inlet and outlet ports. (Material: Choose between stainless steel or brass.)  
A solenoid valve will be added to the chilled water inlet and outlet ports. Solenoid Valve: Same port diameter as the product inlet and outlet ports (material: brass).  
Compression fittings are added to the chilled water inlet and outlet ports. Hose Coupling: Port diameter matched to the product inlet and outlet ports.  
Chilled Water Circuit Water Filter Water Filter A Assembly Filtration Degree:
5µm
 
Water Filter A Assembly Filtration Degree:
10µm
 
Water Filter A Assembly Filtration Degree:
20µm
 
Water Filter A Assembly Filtration Degree:
50µm
 
Water Filter A Assembly Filtration Degree:
100µm
 
Deionizer for Chilled Water Circulation Circuit Deionizer F Assembly Water Quality:
10µS/cm
or lower
       
Deionizer H Assembly  
Deionizer G Assembly        
Deionizer for Chilled Water Circulation Circuit Deionizer Assembly for Supply Water    
Cooling Water (Condenser Circuit)
Inlet/Outlet Open/Close
※ Model names ending with "W" are targeted for water cooled chillers.
Gate valves are added to the cooling water inlet and outlet ports. チラー標準の口径、真鍮または SUS    
Cooling water inlet and outlet ports have solenoid valves added. Solenoid Valve: Same port diameter as the product inlet and outlet ports (material: brass).    
Compression fittings are added to the cooling water inlet and outlet ports. Compression Fitting: Port diameter matched to the product inlet and outlet ports.    
Bypass Circuit The bypass circuit is operated by manually opening and closing the cooling water circuit valves. Built-in, and internal on the RKE. (Built-In)
Power Supply and Control Primary Power Supply Voltage Three-phase 200 V (50/60 Hz), three-phase 220 V (60 Hz)    
Three-phase 230 V (50 Hz), 380/400/415/440/480 V (50/60 Hz) The autotransformer is installed externally. G models do not include casters.  
Overload Safety Devices Built-in overload safety device. RKE2200 models have an earth leakage breaker ※ Available as a manufacturer option on RKE 750 and 1500 models.        
Power Outage Recovery Operation Setting Selects the product recovery pattern after a power outage. Manual recovery / Automatic recovery / Remote operation priority The action taken after recovery can be chosen from the operation panel.  
Operation Action Settings Can choose between "Local" and "Remote" operation. Can select from the operation panel.  
Alarm Signal Output Options Can choose the contact state of the remote alarm signal output. (Relay contacts either OPEN or CLOSED during an alarm condition.) Can select from the operation panel.  
Audible Alarm Enable/Disable Audible alarm for alarm/warning conditions enabled/disabled option. Audible alarm can be enabled or disabled via the operation panel.  
Liquid (Chilled Water) Temp Upper/Lower Limit Warning Option The method of abnormal liquid (chilled water) temperature detection can be selected. Can enable or disable the alarm and standby sequence for relative value and absolute value alarms.
※ Regarding the standby sequence, the alarm will be output after startup until the liquid temperature has initially reached a normal value and then later goes outside the normal range.
Can select from the operation panel.  
Liquid (Chilled Water) Temp Upper/Lower Limit Warning / Absolute Value Upper Limit The warning will occur if the liquid temperature goes above the set temperature (2 to 40 ℃) regardless of the actual set water temperature.
Will be enabled when the absolute values for "Liquid (Chilled Water) Temp Upper/Lower Limit Warning" have been selected.
The water temperature setting can be set from the operation panel.  
Liquid (Chilled Water) Temp Upper/Lower Limit Warning / Absolute Value Lower Limit The warning will occur if the liquid temperature goes below the set water temperature regardless of the actual set water temperature.
Will be enabled when the absolute values for "Liquid (Chilled Water) Temp Upper/Lower Limit Warning" have been selected.
The water temperature setting can be set from the operation panel.  
Remote Control By connecting a remote control to the product, the product can be run and other operations can be conducted (limited control) from a control panel in a remote location. Operating parameters can also be displayed. Remote Control Set C  
Max. cable length: 20 m  
Max. cable length: 50 m  
Max. cable length: 100 m  
Communications Functions Communications Interface and Software    
Communications Device Address Enables communications functions and selects the address number of the unit when multiple units are connected together.
The address no. can be arbitrarily set from 0 to 31.
   
Settings Lock Locks and prevents changes to the water temperature setting and other parameter settings. Can choose whether or not to allow changes to the set value from the operation panel.  
Temperature Warning Signal Output Option Determines the open/closed state of contacts when a temperature warning signal is present. Can choose from the operation panel whether the relay contacts during an alarm condition are ON or OFF.  
External Signal Operation Operation signal terminals No-Voltage Contacts  
Voltage output
(200 V output)
 
Alarm Signal Contacts No-Voltage Contacts  
Voltage output
(200 V output)
 
Remote Operation
(No-voltage contacts)
Max. cable length: 20 m  
Max. cable length: 100 m  
Remote Operation
(24 Vdc Output)
Max. cable length: 20 m
Circuit board takes 24 Vdc input power.
 
Max. cable length: 100 m
Circuit board inputs are activated via a 24 Vdc input actuated relay on the circuit board.
 
Remote Operation
(200 Vac Input)
Max. cable length: 20 to 100 m
Circuit board inputs are activated via a 200 Vac relay on the circuit board.
 
Other CE Marking CE Compliant Models  
Casters With stopper 2 locking freewheeling casters and 2 non-locking freewheeling casters  
2 free-wheeling casters, 2 fixed casters (G2) (G2)
4 free-wheeling casters  
External Surface Coating and Thickness Powder Coating: 30µm    
Salt Corrosion Prevention Spec.
(Acrylic resin coating of at least 45 µm thick.)
External screws are stainless steel. Condenser and refrigerant piping are treated with a corrosion-resistant coating.  
Color Designation

(Specified Munsell No. or JPMA (Japan Paint Manufacturers Association) No.

Melamine resin coating of at least 15 µm.    
For other paint/coatings    
  Case by Case
Packaging for Export Basic Plywood Packaging Please consult your dealer for details regarding JIS standard packaging.  
Water Temperature Control Precision ±0.1℃          
Heating Function Used to raise the temperature during product startup. (Built-in 200 Vac electric heater.)

ON/OFF control to the set fluid temperature minus 2 ℃ ± 0.5℃.

Heating output: Selectable among 2/3/4/5 kW. (Ext. dimensions modified)
Low-Load Response When high-precision control is required at loads below the minimum required amount. Optional Heater Control  
CCV
Circuit Added
       
Inspection Manual Japanese    
English    
Test Results Chart Japanese    
English    
Witnessed Inspection      
Replaceable Dust-Proof Filter   On-Site OP    
  1. Cooling capacity reduced only by the amount of heat generated by the pump.
  2. The water tank cannot be directly connected.
  3. Max. decrease in cooling capacity is 10 %.
  4. Standard model use a copper alloy for wetted parts.

<Note>
Specifications for optional factory equipment may change without notice. Thank you for your understanding.