ORION prduces a variety of products geared towerd making our Inverter Chillers meet the wide-ranging needs of all of our customers.
Intelligent Touch Panel
Various settings and operating conditions can be visually and intutively chaecked and operated via the touch panel controller. The displayed language cn be changed to English, Japanese or Chinese.
Touching the "Measured Liquid Temp." button will change the display to the Graph Screen where changes in liquid temperature will be graphed over a particular time period (up to 53 hours) in order to better aid in liquid temperature management.
Unit Operating Rate (Power Indicator)
The compressor operating state is indicated on a 10 level ber graph which shows the level of energy saving at a glance. Touching the "Op. rate" button brings up the Monitor Screen where operating conditions can be easily checked.
Measured Pressure
Touch "Measured Pressure" to change the discharge pump control option between frequency, flow rate, and pressure.
Menu
Touching "Menu" will bring up a menu of useful functions for easy confirmation and setting of Parameters, Alarm Histry, Main Components, Accumulated Time, Time Function, etc.
Timer Setting
Touching "0:00" on the display allows stop and start timesto be set. Actions can be repeated or set according to the day.
Easy Maintenance / Alarm Display
Alarm numbers are displayed when alarm conditions occur.
Touching the "Details" will show details about the alarm and suggestions on how to deal with it.
The display language can be changed.
English
Japanese
Chinese
Liquid Temp Upper / Lower Limit Warning
A warning message can be displayed or an audible alarm sounded when the liquid temperature goes beyond a set upper or lower limit beyond the set temperature.
Earth Leakage Breaker (ELB)
To help insure safety, as a preventive measure, the unit includes an earth leakage breaker as standard equipment.
Please see the "Equipment (Standard / Optional) List" below for details.
Accessory (Sold Separately)
We have a wide-ranging lineup of accessory (sold separately) to meet every need.
Water Filter Equipment
Use to prevent clogging in the water circuits of your chiller or other equipment and can also be used as a prefilter for water purification equipment.
Configuration for use with RKE22000B-V models and higer are special order items.
Can be replaced by removing the 1×1/2B adapter bushing.
Operate with a chilled water pressure of 0.50MPa or below.
External Dimensions (Units: mm)
Model
Water Filter: A-Assembly
Water Filter: B-Assembly
Water Filter: C-Assembly
A
(435)
(405)
(449)
B
458
708
715
C
197
197
197
D
312
562
565
E
103
103
103
F
423 min.
673 min.
680 min.
G
Rc1/2
Rc1
Rc1・1/4
Tap the image to enlarge it.
Stand Mount
Works with all fillters, Deionizer D-Assenbly, and Deionizer E-Assembly.
2 fiiters can be mounted one over the other on a single stand allowing for space saving configurations, such as having a water filter mounted over an ion exchange filter.
Dimensions (Units: mm)
Ion Exchange Resin Purifying Equipment
For Circulating Water Systems
When installed as a bypass circuit within the chilled water circulation circuit, it can prevent rises in electrical condeuctly in the circulating water.
Spare deionizer※3
ball valve, mounting hardware
hose nipple, hose band
tee coupling, nipple, hose
Mounting bracket, resin nipple, socket,
bushing (preassembled on the filter)
filter removal wrench
Processing capacity figure based on water source standard purity level of 150μS/cm. Capasity may vary according to water quality.
Processing capacity is not based on circulating water flow system. Ion exchange resin lifespan and water quality may fluctuate depending on the properties of the wetted parts and suefaces, as well as the particular working environment.
It is recommended that the initially supplied water be either water that has been purified by having passed ehrough an ion exchange resin, or be commercially purchased deionized water. If tap water (or a similar grade of water) is used, the effective life of the ion exchange resin will be greatly reduced. In this case, please replace the ion exchange resin with the apare soon. (Ion exchange resin assemblies A, B, C, and F only.)
Ion exchange resin assemblies D and E are wall mounted. Please confirm that there is a suitable installation place before installing the filter. A stand mount is available as an accessory (sold separately). (The mounting hole positions of Ion Exchange Resin D and E assemblies are the same as the mounting hole positions on Water Filter A and B assemblies respectively. Please refer to the Water Filter Equipment page for details regarding dimensions.)
on Ion Exchange Resin D and E assemblies, if there is a chance that the water pressure within the purification vessel will exceed 0.2MPa, a pressure reducing valve should be installed.
Avoid installing the ion exchange resin where it will be in direct sunlight or in places where there is a risk of it being damaged.
For Water Supply and Purification
Can suppress sharp rises in electrical conductivity of circulating water that occurs when supplying water to the water tank.
Specifications
Tap the image to enlarge it.
Model
Model Deionizer for Water Supply
Applicable Pulifier
AP-10
Processing Capacity※1※2
Apporox. 2200
Water Quality
μS/cm
1 or less
Working Water Pressure
MPa
0.34 or less※3
Working Water Temperature
℃
5 to 40
Dimensions
Φ165, H: 851mm
Unit Mass
kg
Approx. 15
Inlet Connection
Universal Faucet adaptor
Outlet Connection
Braided hose (Φ12 × Φ18)
Comments
Electrical conductivity gauge (0 - 3μS/cm) included
Flow regulating value (2.2L/min) included
3 anchor bolt holes (Φ10mm × 3)
For water tank supply and replenishment.
Proccessing capacity figure based on water source standard purity level of 200μS/cm. Actual proccessing capacity may change depending on water quality, temperature, etc.
If there is a chance that the water pressure within the vessel will exceed 0.34MPa, a pressure reducing valve should be installed.
Avoid installation of the deionizer where it will be in direct sunlight or in place where there is a risk of it being damaged.
Remote Control (Wired)
Remote Control Sets include cables. Tha set model number differs depending on the cable length. (Max cable length: 20m, 50m, 100m.)
At time when the liquid temperature is rising, the heater should be used if high-precision control is required even when the load is low (and there is not the minimum amount of heat required for inverter control).
Discharge Pump for High Head Applications
High flow rate pump built-in. A built-in pump supporting a higher head specification is available.
Cleanroom (Leakage Alarm Spec.)
Leakage Alarm Spec. models are available for use in cleanrooms.
Leakage Detection Spec.
If for some reason a water leak occurs, an alarm will be activated.
Please see the "Equipment (Standard / Optional) List" below for details.
External Surface Paint Thickness
The thickness of the applied outer surface paint can be changed to suit particular applications or needs.
Meets the Demands of World Markets
CE Marking, Other International Standards
Please consult our sales staff regarding any of your particular needs. > Contact Us!
Equipment List (Standard / Optional) List
Model Name (RKE Series) Column Notation Key
-
Not Supported
●
Accessory (Sold Separately)
★
Special Specification
Click for further information.
Equipment List
Tap the image to enlarge it.
Function List
Model Name (RKE Series)
Item Detail
Comments
3 7 5 0 B | V
5 5 0 0 B | V
7 5 0 0 B | V
1 1 0 0 0 B 1 | V
1 5 0 0 0 B | V
2 0 0 0 0 B | V
3 0 0 0 0 B | V
3 7 5 0 B | V W
5 5 0 0 B | V W
7 5 0 0 B | V W
1 1 0 0 0 B 1 | V W
1 5 0 0 0 B | V W
Operating Environment
30 to 40% ethylene glycol solution. ※1
Operation Possible
Deionized Water. Electrical Conductivity: 1µS/cm or higher
※3
Working Liquid (Chilled Water) Temperature
3 to 35℃
0 to 35℃
Operable Ambient Temp Range
Low temp area spec.: -20 to 45℃ (Air Cooled), 2 to 45℃ (Water Cooled)
High temp area spec.: to 50℃ Requires Distribution Panal High-Temperature Set
Freeze-Prevention Mode
This function operates the discharge pump in order to prevent water temperature drops and freezing during winter months when unit operations is stopped. When enabled, the discharge pump will operate when the water temperature falls to 3℃ or below.
Standard Equiment
Warm Up Mode
This function will automatically operate the discharge pump when the unit is otherwise not operating when the ambient temperature is low, for example during winter months, in order to prevent the water temperature from dropping too much and in order to help maintain the set water temperature. When this mode is enabled, the water temperature can be set within the temperature range of 10℃ to 35℃ as desired.
Standard Equiment
Low Noise Mode※2
This function will limit the upper speed of the fan ventilation noise level will be decreased.
Standard Equiment
Outside Installation
IPX4 Equiv. Rating
Snow Protection Mode
When enabled, and when the unit is stopped, the fan will periodically and automatically start in order to blow fallen snow from the upper exhaust port.
Standard Equiment
Snow Protection Hood
Prevents falling snow from entering the fan intake.
Wind Shield
Consider a wind speed is 8m/s or higher as a guideline.
Cleanroom (Leakage Alarm Spec.)
In addition to the standard specification, leakage sensors, pressure resistant piping, refrigerant piping insulation, and water piping insulation are added.
Water Leakage Detection
Leak detector built in.
Vibration Reducing Base
Reduces transmission of vibration from the chiller.
Chilled Water Circuit
Discharge Pump Specs.
High flow rate pump built-in. Can replaces the built-in high pressure pump.
Relief Valve (Pressure Valve)
Can provide equipment-side pressure protection.
Water Tank Water-Level Alarm (Lower limit alarm)
Used to avoid water shortages due to evaporation.
Standard Equipment
Water Supply Port Open / Close
A ball tap is provided in the water tank in order to maintain a uniform water level.
Standard Equipment
A ball valve is added to the water supply port.
Chilled Water Inlet / Outlet Open / Close
Gate valves are added to the chilled water inlet and outlet ports.
Compression fittings are added to the chilled water inlet and outlet ports.
Chilled Water Circuit Water Filter
Water Filter A Assembly
Water Filter B Assembly
Water Filter C Assembly
Deionizer water Equipment for Chilled Water Circulation Circuit
Deionizer C Assembly
Deionizer D Assembly
Deionizer E Assembly
Deionized Water Equipment for Chilled Water Supply and Supply Circuits
Purification Assembly for supply water.
Cooling Water (Condenser circuit) Inlet / Output Open / Close
Gate valves are added to the cooling water inlet and outlet ports.
Compression fittings are added to the cooling water inlet ond outlet ports.
The unit comes with a built in multipurpose overload and short circuit protection breaker.
Current Sensitivity: 30mA
Current Sensitivity: 100mA
Current Sensitivity: 30mA
Current Sensitivity: 100mA
Intelligent Touch Panel Display Function
Time and Date Display (Year/Month/Date/ Hour:Min (Day) / Measured Water Temperature, Set Water Temperature, and a graph of the measured water temperature.)
Parameter Mode Display / Water Pressure・Flow Rate・Discharge Pump Operating Frequency and Operating Conditions Display. Japanese・English・Chinese Display (Selectable)
Standard Equipment
Operation Action Settings
Can enable or disable operation from among the main unit, remote control, external communications, or remote switch.
Standard Equipment
Independent Pump Operation / Control Setting
Pump-only operation can be enabled / disabled via the main unit, remote control, external communications signal, or the remote switch.
Standard Equipment
Power Outage Recovery Operation Setting
Can choose the recovery pattern after power outage.(Manual recovery / Automatic recovery / Remote operation priority)
Standard Equipment
Settings Lock Setting
Control from each of the following can be enabled or disabled: Main Unit, Remote Control, or External Communications Signal.
Standard Equipment
Audible Alarm Enable / Disable
Audible alarm can be enabled or disabled for each audible alarm or warning.
Standard Equipment
Action on Compressor Related Alarm
In cases where an alarm signal has been generated, this setting allows the user to choose whether the unit will completely shut down or if components that are able to operate will continue to do so.
The method of abnormal liquid (chilled water) temperature detection can be selected. Can enable or disable the alarm and standby sequence for relative value and absolute value alarms.
Regarding the standby sequence, the alarm will be output after startup until the liquid temperature has initially reached a normal value and then later goes outside the normal range.
The warning will occur if the water temperature goes above this set temperature regardless of the actual set water temperature. Will be enabled when the absolute values for "Liquid (Chilled Water) Temp Upper/Lower Limit Warning" have been selected.
The warning will occur if the water temperature goes above this set temperature regardless of the actual set water temperature. Will be enabled when the absolute values for "Liquid (Chilled Water) Temp Upper/Lower Limit Warning" have been selected.
Standard Equipment
Time Elapsed Warning: Time Setting
A warning will be output if the select time is exceeded. This will be useful, for example, maintenance timing management.The unit can continue to operate when this occurs.
Standard Equipment
Communications
USB and RS-422A / 485 communications allow operation and setting changes from a remote location. To connect multiple units, set the communication device address number to any number between 0 and 31.
Standard Equipment
Remote Control (Wired)
By connecting the remote control, the product can be operated from a remote location, and various settings can be changed as if using the touch panel.
Centrl Chiller Controller
By connecting the Central Chiller Controller to mulitiple units, individual units can be operated, and their settings changed. (Registration of up to 4 groups with 4 units per group is possible.)
Remote Control Terminals
Remote Operation (No-voltage contacts) ※5
Standard Equipment
Remote Operation (24Vdc Output)※5 Only available as factory installed options.
Remote Operation (200 Vac Input) ※5 Only available as factory installed options.
Signal Output Terminals
Operation Signal
Standard Equipment
Alarm Signal※4
Standard Equipment
Alarm Signal Output Options
Can choose the state of contacts of the remote alarm signal output. (Contact either On or OFF during alarm condition.)
Standard Equipment
Temperature Warning Signal Output Option
Determines the open / closed state of contacts when a temperature warning signal is present.
Standard Equipment
Settings Lock
Changes to the water temperature setting and other parameter settings can be locked out..
Standard Equipment
Other
Casters
2 locking freewheeling casters and 2 non-locking freewheeling casters
※6
※6
With lock
With leveling foot
External Surface Coating Thickness
Polyester resin, min. 30μm
Standard Equipment
Polyester resin, min. 45μm (Salt-Corrosion Prevention Spec.)
Color Designation
Specify the color designation as a JPMA No. or Munsell No (including a color sample).
Packaging for Export
Basic Plywood Packaging
Water Temperature Control Precision
±0.1℃
※8
Standard Equipment
Heating Functionary
Used to raise the temperature during unit startup. (Built-in 200Vac electric heater.)
ON / OFF control to the set liquid temperature minus 2℃ ±0.5 °C.
Inspection Manual
Japanese
English
Test Results Chart
Japanese
English
Initial Inspection
Note that there will be a 10% reduction in cooling capacity.
Note that there will be max. 20% reduction in cooling capacity.
Copper alloy is used for wetted parts on standard units.
In addition, there are contacts for the temperature warming signal.
There are 2 operating modes -- unit operation, and pump-only operation.
Comes as standard equipment on -G2 spec models only.
Also available as a special specification product.
Please consult your dealer if high precision control is required even under low loads (the minimum amount of heat required to maintain inverter control).