Precision Air Processor [For Temperature and Humidity Control]

PAP®mini (Compact Series) Energy Saving Precision Air Processor

ORION's Thorough Investigation of Energy Saving and High Precision Technology
We've achieved a higher level of temperature and humidity controlled, clean environment.

Typical Applications: Precision Measurement, Analysis Equipment, Test Equipment

PAP®mini Product Information
Catalog Download

Point 2: Built-In Intelligent Monitor

Easy to use function keys offer expanded operability.


F001 Automatic Recovery After Power Outage Option
F002 RUN/STOP Operation Option
F003 Alarm Signal Output Option
F099 Settings Lock Option
F100 Controlled Outlet Air Temp Warning

Built-In Self Diagnostics

Of Course Includes Individual Warning/Alarm Indications

Built-In External Communications Capability

Built-In Support for 3 Types of Communications Standards
(RS-232C, RS-422A, RS-485)

Temperature Control Type
Temperature and Humidity Control Type

Point 3: Easy Installation

You can plan on cleaned, temperature and humidity controlled air where you need it, when you need it. And very easy to move or remove when no longer needed.

As much as a 70% cut in heat output. ※

Extremely low heat output means less burden on the air processor, even when located inside a room.
※ Compared with sustained compressor operation + heater-reheating methods.

Built-In Self Diagnostics

Of Course Includes Individual Warning/Alarm Indications

Built-In External Communications Capability

Built-In Support for 3 Types of Communications Standards
(RS-232C, 422A, 485)

Compact Design

A compact design that fits neatly besides your work desk.

PAP01B Type
PAP01B-KJ Type
Easy Installation!

Single-phase 100 V spec. allows for easy installation in laboratories, etc. (PAP01 Series)

Application Examples

Perfect for every kind of Application Needing Temperature Control

Liquid Dispensing (Pipetting) Equipment

Liquid dispensing equipment is widely used in the fields of biology, chemistry, and medicine. Improved precision can be achieved through temperature and humidity management.

Electronic Balance

Mass measurement in analytical chemistry is generally done using the electronic balance. Allows you to get stable measurement results by preventing subtle changes due to temperature changes.

Electron Microscope

Electron microscope resolutions are at a level of 0.1 nm, and such a working environment demands a uniform range of temperature and humidity. In order to achieve more reliable, higher analytical results, better prepared environmental conditions are indispensable.

Chromatograph

Chromatograph equipment measures the respective constituent contents of a sample. Measurement sensitivity on the order of PPM (parts per million) to PPQ (parts per quadrillion: 1 / 1x10¯¹⁵) and is particularly used in bio-chemistry, pharmaceuticals, and food-related applications. Higher-reliability results can be achieved with high level environments.

ORION can propose a system that meets your application needs. We are always available for consultations.

PAP03C PAP03C-KJ
Performance Possible Temperature and Humidity Setting Ranges※1 ℃,% 18~30 18~30,45~75
Temperature and Humidity Control Precision※2 ℃,% ±0.1 ±0.1,±1.0
Cooling + Heating Capacity (50/60 Hz)※3 kW 1.65/1.85 1.8/2.12
(Maximum cooling capacity) (kW) (1.15/1.35) (1.2/1.42)
Rated Processing Air Flow※1 m3/min 2.0~4.0
Maximum External Static Pressure※4 Pa 110/150 110/150
Environmental Conditions Ambient Temp and Humidity Range (Intake air)※1 ※5 ℃,% 15~40,30~70
Temperature Gradient at Intake ℃/h Within±1
Humidity Gradient at Intake %/h Within±5
External Dimensions (H×D×W)※6 mm 1070×590×480 1350×680×520
Product Mass kg (95) (135)
Controlled Air Outlet Port mm Φ98
Humidification Water Water Quality - Conditioned water (Electrical conductivity: 1 to 10 ℃S/cm)
Max. Moisture Output※7 kg/h - 2.3
Supply Temperature Range - 10~40
Connection - Rc1/4
Electrical Specifications Power Supply※8 V(Hz) Three-Phase200±10%(50/60)
Power Consumption※9 kW 0.75/0.85 2.7/3.1
Current※10 A 3.8/3.8 11/12
Power Supply Capacity※11 kVA 1.4 4.0
Sound Level(50/60Hz) dB 64/65 65/66
Refrigerant R410A
Chiller Compressor Output kW 0.8 0.85
  1. The temperature and humidity control ranges noted do not necessarily indicate the actual possible controllable range. The actual controllable temperature and humidity ranges will depend on the temperature and humidity of the intake air as well as the process air flow rate. Set the processing air flow according to the operating environment.
  2. When the air temperature and humidity are stable at the air intake.
    Noted precision value displayed on the controller is for one point at the outlet port. When operating at the maximum rated air flow (3m3/min).
    There will be temporary fluctuations in temperature for 2 minutes after the product is started due to the oil-return process at that time.
    Also, if the target humidity is high, and depending on the timing of the supply of the humidification water, the precision previously noted may not be able to be maintained.
    In such cases, the amount of fluctuation can be reduced by adjusting parameters related to supply water.
  3. When the intake (surrounding) air temperature and humidity are 30 ℃, 70%, at a processing air flow of 3 m3/min .
  4. When the processing air flow is 3 m3/min.
  5. See the operating manual for details regarding the possible operating range of ambient temperature and humidity.
  6. Height includes the outlet port.
  7. Indicates maximum humidification within the rated control range.
  8. The source voltage phase imbalance should be ±3% or less.
  9. When the intake (surrounding) air temperature and humidity are 30 °C, 70%, at a processing air flow of 3 m3/min and the power supply voltage is 200 Vac.
  10. Maximum value within the product operating range.
  11. The figure noted is when operating at the highest capacity of the normal operating range.
  • Note: Ducting should be insulated and ducting length should be kept as short as possible.(Recommended maximum length: 3 m)